AirStage UTY-DTGG Руководство по установке - Страница 3
Просмотреть онлайн или скачать pdf Руководство по установке для Контроллер AirStage UTY-DTGG. AirStage UTY-DTGG 7 страниц. Touch panel controller
Touch pen
1
Binder
4
31
ELECTRICAL REqUIREMENT
When connecting the Touch Panel Controller, use the following wir-
ing.
Use
Size
Max.1.25 mm
(16AWG)
Power supply
cable
Min.0.5 mm
(20AWG)
Transmission
0.33mm
cable
(22AWG)
External input
0.33mm
cable
(22AWG)
Use
1Φ 50/60Hz 100-240V
Power supply
2 wire + earth (ground)
cable
(Always earth (ground) the unit)
L
W
Transmission
ON
ORKS
cable
compatible cable
External input
Use cable in accordance with local rules for
cable
cable
L
W
*
is registered trademark of Echelon Corporation in
ON
ORKS
the United States and other countries.
Fuse capacity
41
SELECTING AN INSTALLATION LOCATION
41 11
Dimensions
▪
Touch panel controller
main unit and installation plate
Top view
Touch pen
246 (9-11/16)
USB port
Touch
panel
Rear cover
Side view
Front view
198 (7-25/32)
Installation
plate
Rear view
*
For the screw position dimensions of the installation plate, see page 4.
Pen for touch panel con-
troller operation
Prevents dropping off of
the cable
Wire type
2
Type 60245 IEC 57
or equivalent
2
22AWG LEVEL 4 (NEMA)
2
non-polar 2 core, twisted pair
solid core diameter 0.65mm
(1/32 in.)
2
2 core, twisted pair (Max.
cable length : 25m (82ft.))
Remark
5 A
Unit:mm (in.)
Front cover
54(2-1/8)
Side view
66 (2-19/32)
2-Ø17 (21/32)
41 21
Installation restrictions
▪
Surrounding space
Provide the following space when installing touch panel controllers in
a row and also provide the following space from the projecting parts
of the surroundings.
Space necessary at surroundings
100 (3-15/16) or more
200 (7-7/8)
200 (7-7/8)
or more
or more
100 (3-15/16) or more
*
Minimize the horizontal and vertical tilts of the switch box installed
at the installation site in advance.
▪
Installation layout
When installing the touch panel controller, installation layouts such
as these are not allowed.
Left-right sideways
Reversed instal-
installation prohibited
lation prohibited
51
INSTALLING THE TOUCH PANEL CONTROLLER
WARNING
Always use the accessories and specified installation work parts.
Check the state of the installation parts. Not using the specified
parts will cause fall, water leakage, electric shock, fire, etc.
Install at a place that can withstand the weight of the unit and
install positively so that the unit will not topple or fall.
When installing this unit, make sure that there are no children
nearby. Otherwise, injury or electric shock could result.
After this unit is installed, perform a test run to verify that the
device operates normally. Then describe the operation method of
this unit to the customer.
Install a circuit breaker. Not installing a circuit breaker will cause
electric shock or fire.
CAUTION
Before opening the case of this unit, remove all the static electric-
ity accumulated on the human body. It will cause an accident.
When the front cover fixing screws are removed, be careful that
the front cover does not fall off. It will cause an injury.
The circuit boards of this unit are at both the front cover and rear
cover. When a cover is opened, the circuit boards may be dam-
aged by the screwdriver. This will cause an accident.
The front cover and rear cover are connected by wiring. When
disassembling, be sure that the wiring is not stretched.
Do not touch this unit's circuit board and circuit board parts directly
with your hands. Doing so may cause electric shock or injury.
Tightening the mounting screws too tight will damage the case of
this unit.
When inserting the hooks, do not push them in unreasonably. Do-
ing so may damage or deform the claws.
Do not operate the surface of the touch panel with other than the
accessory touch pen or your finger. It will scratch the surface and
cause trouble.
Unit:mm (in.)
200 (7-7/8)
or more
Flat installa-
tion prohibited
En-2