AirStage UTY-VLGX Руководство по установке - Страница 7
Просмотреть онлайн или скачать pdf Руководство по установке для Медиаконвертер AirStage UTY-VLGX. AirStage UTY-VLGX 7 страниц. Vrf system network convertor
7.
Turn the power off and on or press SW7 (reset
button) to exit from address setting mode.
This time, please refer to the "7. TURNING ON
THE POWER" for the content displayed in D19 LED.
9. INITIAL SETTING (SOFTWARE)
The initial settings for the Network Convertor must be
performed before the commissioning. Please see the
attached "Application Manual - Tool for Network Convertor"
and complete the settings.
10. BINDING & COMMISSIONING (NOTICE)
(1) It is necessary to make an XIF (External Interface File) for
binding.
(2) The commissioning doesn't end if the number of Indoor/
Outdoor Unit of the XIF fi le made with Tool of Network
Convertor is not in consistency with the number after
Indoor/Outdoor Unit Address is registered.
In addition, the Network Convertor can not operate
normally if the number of Indoor/Outdoor Unit of the XIF
fi le is not in consistency with the number after Indoor/
Outdoor Unit Address is registered.
(3) Binding and commissioning must be performed again if
the number of connecting units (indoor/outdoor units) has
changed after system operation. Please always register the
allocation information that is in consistency with the VRF
system, Functional Block in the Network Convertor and
the Network Convertor, if register the changed XIF fi le in
according to the "Tool for Network Convertor".
Important:
Network Convertor will not operate if,
•
VRF network system address (Indoor & Outdoor units
address) allocation information are not registered to
Network Convertor.
•
XIF data information and VRF network system address
allocation information must not be same.
•
Binding & Commissioning is not executed.
•
The ID number registered on Network Convertor is
different from the ID number when XIF fi le is created.
•
Two or more Network Convertors are connected to BMS,
and these are set the same ID number.
11. LED DISPLAY (D19)
(1) Normal code
Normal code
Normal mode
Set state of
"Tool for Network Convertor"
Address setting mode
Under maintenance
FB and unit address allocation
information is registered with
"Tool for Network Convertor"
FB* : Functional Blocks
(2) Error code
Error code
FB and unit address allocation
information is not registered
Main PCB error
VRF Network error
D9 LED lit or blinking
Communication error
(Error of the Network Interface
D9
D9
Device on VRF System)
Communication error
D14 LED lit or blinking
(Error of the Network Interface
D14
D14
Device on BMS)*1
When V series or S series is
connected
*1. D14 is ON for 1 second, OFF for 1 second, and
repeats. When D19 is in Normal mode, Commissioning
is unset.
Contents
Contents
En-7