LOCATION AND SHIELDING OF CONNECTING
FLUEPIPES
Connecting fluepipes should be used only to connect appliances
to their chimneys. They must not pass through any roof space,
partition, internal wall or floor, except to pass directly into a
chimney through either a wall of the chimney or a floor supporting
the chimney. Connecting fluepipes should also be guarded if they
could be at risk of damage or if the burn hazard they present to
people is not immediately apparent.
Protecting combustible material from uninsulated fluepipes for solid fuel appliances
Elevation
without shield
Shields should either:
a) extend beyond the fluepipe by at least 1.5 x D; or
b) make any path betweeb fluepipes and combustible
material at least 3 x D long.
AIR REQUIREMENTS AND ASSESSING AIR
PERMEABILTY OF OLDER DWELLINGS IN RELATION
TO PERMANENT VENTILATION REQUIREMENTS
It is important to note for proper operation, this appliance requires
room air to function efficiency. Therefore, a calculation of the air
requirements should be performed before and after installation for
proper and efficient operation of this product.
22
Connecting fluepipes should be located so as to avoid igniting
combustible material. Ways of meeting the requirement include
minimizing horizontal and sloping runs and:
•
•
Plan without
Elevation
shield
with shield
As a guide, this appliance requires 3410mm² of permanently open
vent in a well-sealed house, but this reduces to 660mm² for a
house with much higher air permeability. It is unlikely that a house
built before 2008 will be well-sealed unless extensive measures
have been taken to improve air tightness.
Older houses are unlikely to have been tested but are unlikely to
achieve an air permeability of less than 5.0 m3/(h.m2) at 50Pa
unless the building fabric has been substantially upgraded.
Following the guidance as noted above where the connecting
fluepipe is a factory-made metal chimney is at least equal
to designation BS EN 1856-1:2003 and installed to BS EN
15827-1; or
Separation by shielding in accordance with the diagram below:
Indicates combustible
INSTALLATION
Air space of at least 12mm
between non-combustible
shield and combustible
material
Plan with
shield
material
6720818040 B 04/2017