Fig. 9 — Routing Power Lead through Current
Transformer (CT)
Fig. 10 — Service Hybrid Overload Wiring — 5-Pin Plate Assembly or 6-Pin Plate Assembly for
CUSTOMER WIRING
ROUTED THROUGH
THE CT
SEE DETAIL
IN FIG. 9
Universal Compressor
4
Service Hybrid Overload Wiring — 5-Pin Plate
Assembly or 6-Pin Plate Assembly for Univer-
sal Compressor
1. Connect one control circuit lead to module connection
11 located on top of the module as shown in Fig. 10.
Use a fork terminal or stripped and tinned wire to pre-
vent fraying. Torque module connections to 12 lb-in.
(1.35 Nm) maximum.
2. Determine module power supply voltage by referring to
the 6th digit in the part number located on the left side
of module (06DASB****). The supply voltages are 115/
230 vac and 24 vac and correlate to digits B and C re-
spectively. Connect 2 module power leads to module
connections L and N using a fork terminal or stripped
and tinned wire to prevent fraying. Refer to module
front label for further power supply requirements.
Torque module connections to 12 lb-in. (1.35 Nm)
maximum.
3. Route 2 power leads (L1 and L3) through current trans-
formers (CTs) as shown in Fig.10. See detail in Fig. 9.
4. Once power lead L3 is routed through CT, make termi-
nal plate connections as shown in Fig. 10. (Terminal
pin 7 is not used but may be present on 6-pin assem-
bly.) Refer to Terminal Plate Wiring section for connec-
tion details.