OPERATION

1. Check all wiring from the electrical service line to the dehumidifier.
2. Check all wiring between the dehumidifier and the Model A76 Control.
TURN ON & SET MODEL A76 CONTROL
1. When power is supplied to the dehumidifier, the control will display the measured humidity and initially be in OFF Mode.
2. Press the ON button on the Model A76 Control.
3. The default humidity setting is 60%RH. Use the UP/DOWN arrow buttons to adjust the humidity setting. The first button press will display the
current setting and SET on the LCD display. Each subsequent push of the buttons will change the setting by 1%RH.
4. When desired humidity setting has been set, the control will return to Normal Mode, displaying the measured humidity 5 seconds after the last
button press/release.
SEQUENCE OF OPERATION
When the measured humidity is greater than the setting, the control will activate the dehumidifier output, the dehumidifier will begin dehumidifying,
and ON will blink on the Model A76 LCD display. When the measured humidity falls 3% below the setting, the control will deactivate the dehumidifier
output, the dehumidifier will stop dehumidifying and the LCD will display a solid ON.
CONTROL LIMITS
If the control measures a dew point below 40°F OR a temperature above 99°F, the control will deactivate the dehumidifier output, if actively
dehumidifying, the dehumidifier will stop dehumidifying and ON and
the measured dew point is greater than 45°F or the measured temperature is below 94°F, depending on what control limit was exceeded.
Reference the Model A76 Installation Instructions for additional information.
ALTERNATE CONTROLS
If using an alternate control, reference the Installation and Operating Instructions supplied with the control.

MAINTENANCE

FILTER
After initial installation, the air filter should be replaced every 6 months. Remove the filter access panel to remove and replace the filter.
DRAIN
The drain should be checked periodically to ensure there are no blockages or air lock in the drain system.
CONTROL
The surface of the Model A76 Control can be cleaned with a damp cloth or non-abrasive general cleaner. Do not spray any liquid directly on the
control. Spray water or cleaner onto a soft cloth and gently wipe the surface of the control.
*
will blink on the LCD screen. The control will resume normal operation when
9