7. Burner Operation Data
– Maximum input: 990 kW/m (when air DP across burner is 2.5mbar)
– Minimum input: 24 kW/m
– Fuel inlet pressure: 22 mbar
– High fire flame length: 1100mm. (when air DP across burner is 2.5mbar, the lower air
DP, the longer flame)
– Upstream temperature limit: –30°C to 400°C
– Downstream temperature limit:800°C
– Ignition: Direct Spark Ignition or pilot ignition
– Flame detection: Flame rod or UV scanner
– Fuels: Natural Gas, Propane, hydrogen
Remark:
Air DP across burner means air pressure difference between burner inlet and chamber, gas
pressure different means gas pressure difference between burner inlet and chamber.
8. Performance Curves
The operation and emission curves of the ANM75 series burner is shown in figure 2 and
figure 3.
Fig 2. ANM75 Series Burner Operation
Fig 3. ANM75 Series Burner emission
9. Burner datasheet
The input and flame length curves of the ANM75 series burner is shown in figure 4 and 5
Anderson Thermal Soluions(Suzhou)Co. ,Ltd.