Atkinson Electronics GSCM-MINI-50 Руководство - Страница 7
Просмотреть онлайн или скачать pdf Руководство для Блок управления Atkinson Electronics GSCM-MINI-50. Atkinson Electronics GSCM-MINI-50 12 страниц. Generator start control module - mini (2 wire to 3 wire)
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
GSCM-mini FAULT SHUTDOWN CONDITIONS
The GSCM-mini detects Four (4) fault shutdown conditions (over/under Hz. detection not enabled until the generator has been running
for 60 seconds) and will shutdown the generator after 10 continuous seconds of Hz. fault condition, locking it out until a power down
reset and power back up. The Fault open collector transistor output (terminal 12) will energize a user supplied remote lamp or DC relay
(not exceeding 300 milliamp coil current) whenever a fault shutdown occurs and will de-energize the relay when the fault is reset. The
shutdown conditions are as follows:
1.
Failure to start with 3 cranking attempts (see Section-1:3, 2:2, & 3:3 ). The Gen. Hz Shutdown LED does a double blink and Fault
LED On continuously.
2.
High frequency (over Hz.) condition. The generator AC frequency is monitored on terminals 9 and 10. If the Gen. Hz. enable
terminal #8 is grounded and the generator output frequency exceeds the 55 Hz fixed threshold for 10 seconds, the generator shuts
down and the Generator Hz shutdown LED blinks rapidly. The "Generator Hz" LED blinks during this 10 second period.
3.
Low frequency (under Hz.) condition. If the Gen. Hz. enable terminal #8 is grounded and the generator output frequency remains
below the 45 Hz fixed threshold for 10 seconds, the generator shuts down and the Generator Hz shutdown fault LED blinks slowly.
The "Generator Hz" LED blinks during this 10 second period.
4.
Auto Start within 30 minutes of Max Run Time shutdown (see Section-4:4 ). The Gen. Hz Shutdown LED does a triple blink and
Fault LED On continuously.
LED DESCRIPTION
1.
Start:
one blink every 5 seconds = Ready mode, looking for a start signal;
one blink every 2.5 seconds = auto start mode operation;
one blink every other second= auto start/stop period,
continuous = manual start signal received;
fast blink = 60 second delay after start signal removed before generator started;
2.
Generator Hz
fast blink = over speed condition;
Shutdown:
slow blink = under speed condition;
double blink = Maximum Crank attempts reached, Failed to Start;
continuous = start function disabled, AC Hz detected before starting;
3.
Run:
continuous = GSCM has a valid run signal from generator;
4.
Fault:
continuous = GSCM is in a fault condition and requires a reset;
5.
K1 & K2:
continuous = Status of K1 and K2 Relays "ON"
SPECIFICATIONS
SIZE & WEIGHT: 5.13" L x 2.853" W x 1.35" H, 20 OZ
MOUNTING:
2 screws through tabs,
Mounting holes 3.5" center to center
POWER:
12VDC only
Quiescent current < 10mA
Relay current < 25mA ea.
TERMINALS:
0.250" spade lugs
MANUAL INPUT: B+ (12VDC) input = on condition
Open input = off condition
BATTERY INPUT:
0-60V DC
AUTO START/
STOP THRESHOLD: 12V System 11.5V,
24V System 23.0V,
48V System 46.0V,
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
Start
Stop
13.8V
27.6V
55.2V
Distributed by:
RELAY CONFIG.: Open input = Momentary Crank
(TERMINAL 6)
Grounded input = Maintained Crank
B+ (12VDC) input = Ignition & Crank
FREQUENCY INPUT: 120-240V AC 0-100 Hz
OUTPUT RATINGS: Qty. (2) 10 Amp 28V DC relay contacts
K1 has 38vdc MOV across contact
Qty. (2) Open collector NPN
transistors, Max. 300mA each
FAULT DETECTION: Start Failure, (3 attempts)
Over Hz condition (10 seconds)
Under Hz condition (10 seconds)
AMBIENT TEMP: -40 to 858C
GSCM-MINI-50HZ
SECTION - 7
SECTION - 8
SECTION - 9
REV 5/08