Dresser iCIP 300 Series Руководство по установке и эксплуатации - Страница 8
Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Водяной насос Dresser iCIP 300 Series. Dresser iCIP 300 Series 14 страниц. Intelligent chemical injection pump
Figure 15 – Solar Pump User Terminal Software
•
The second or "Series 200" or "Data Logging" module
Event kernel, with timers and I/O triggering will be able
to capture or record raw data at a maximum of 1440
minutes (20,000 record capacity) of on-site pump data,
such as power consumptions, battery charge condition,
solar panel output wattage, pumping total volume,
ambient temperature, well pressure, tank level, alarm or
security protocol. Several concrete base classes for
common sensor configurations, including: Waiting
Serial Channel -- waits for data to become available and
uses a regular expression to extract values from serial
devices Polling Serial Channel -- wakes up periodically,
reads any available bytes from the serial port, and uses
a regular expression to extract values. This data can be
accessed and retrieved using an on-site laptop via the
RS232 bus with the User Terminal iCIP software.
Logging and
Communication
module install
location
Figure 16
•
The "Series 300" or "Communications" Module will be
able to remotely access or communicate live pump data
from the controller/system via a MODBUS over a
non-Isolated RS485 half duplex (bi-directional) serial
communication port and display on a screen or monitor
live conditions of on-site pump data. RS-232
Communication Baud Rates or BPS (bits per Second)
Transmission peeds available: 1200, 9600, and 19200.
•
The fourth or "Series 400" will integrate both the Data
Logging and Communications Modules into one
module. The live data can be easily accessed,
downloaded into a CSV format spreadsheet or log file
for further review.
Firmware Installation
An install / uninstall Firmware Upgrade Options Module is
required and will be provided with reference to product Solar
Solutions Series installation Identification or Serial Number.
This module will be available in the event of a firmware
upgrade to the iCIP
™
controller.
Upgrade Firmware on iCIP Controller
1.
Insert Firmware Upgrade Options module into Options
connector on front of iCIP controller.
a.
The display should read Upgrade PGM.
2.
Move the joystick to the right.
a.
The display should read WAIT.
b.
The display will next display the version of the
firmware saved in the module.
3.
Move the joystick to the right.
a.
The display should read ARE YOU SURE.
4.
To upgrade the firmware press the center of the joystick.
5.
The display should read 1 then 2 and finally DONE.
6.
Remove the Firmware Upgrade Option Module to
complete the upgrade.
Motor Controller Enclosure
A covered NEMA rated enclosure housing has been provided
to protect personnel from accidental exposure to electrical
components and also provide a degree of protection to the
electronics from the environment. Avoid static discharge
into the circuitry when servicing or connecting electrical
connections.
Solar Converters
These charge controllers use the latest in technology to
further boost the performance current produced by the solar
panels with the aid of micro processor solar power
management tool. The result is a highly efficient solar power
converter. When solar energy is being produced using solar
8