Electrolux CS910CS Руководство пользователя - Страница 3

Просмотреть онлайн или скачать pdf Руководство пользователя для Вентиляционная вытяжка Electrolux CS910CS. Electrolux CS910CS 6 страниц.

INSTALLATION

PRE-INSTALLATION
Before installing the cooker hood, peel off any protective
plastic covering and remove polystyrene from inside behind
the fan motor. See diagram below.
LOCATION
The underside of the hood body must be a minimum
of 600mm* above an electric cooktop and 650mm*
above a gas cooktop and a maximum height of 800mm.
*If the instructions of the hob specify a greater distance than the minimum above,
then that shall be the minimum height for installation.
5
User manual_CS910CS
INSTALLATION
1. Using a spirit level mark a vertical centre line on the
wall where the hood is to be positioned, and a
horizontal line at the hood base position (refer
Fig. 6 below).
2. Mark the location for flue cover wall mounting brackets
and rangehood mounting points and anti-tilt fixing
points above the hood base using the hood base as
the reference point (Fig. 6 below).
25mm
235mm
270mm
250mm
250mm
36mm
580mm
Min. 650mm
Max. 800mm
• Recommended working heights
• Cover flue mounting bracket locations
• Telescopic cover flue fixing points
Fig. 6
3. Install flue cover wall mounting brackets with suitable
fixings. Install suitable screws for rangehood mounting
points (to support a total weight of 30kg) to the wall as
marked (Fig. 7).
INSTALLATION
ceiling
Fig. 7
4. Remove the protective plastic film from the hood body
and hang hood on the mounting screws then secure at
the anti-tilt locations as indicated in Fig. 6 & 7.
5. Fix exhaust transition duct using screws supplied
(Fig. 8).
Depending on the preferred installation/ducting mode,
follow step 6a or 6b below.
6a.Recirculating mode (Fig. 9). Using the centre line,
secure the recirculating T-piece to the wall with suitable
screws/fixings (optional kit AR910RK). Install flexible
pipe between T-piece and the exhaust transition duct.
Use cable ties or suitable duct tape to secure flexible
pipe to T-piece and transition duct (Fig. 11).
NOTE: When installed in recirculating mode, it is
recommended to use a carbon filter (included in
recirculation kit AR910RK) to prevent odours being
emitted back into the room.
6b.Ducted mode (Fig 10.) The canopy rangehood has
been supplied with flexible flue pipe and duct transition
piece, alternatively a 150mm diameter non-combustible
flue pipe can be used. Continue the centre line to the
ceiling. Fit preferred flue pipe to the fan transition duct.
Use cable ties or suitable duct tape to secure flexible
pipe to the transition duct.
NOTE: For ducted mode, extend the flue pipe through
the roof to external 'china hat' to vent exhaust externally.
Do not vent into the ceiling cavity.
NOTE: To ensure optimum performance of the
rangehood, the use of rigid ducting is recommended.
The use of bends should be avoided. Rigid flexible
ducting is suitable, although loose flexible ducting is
unacceptable. All ducting must be fire retardant.
Fig. 9
Fig. 8
Fig. 10
6
28/11/2012