HOW TO SET THE CONDENSATE DRAIN OPEN & CLOSED TIME
(LOCATE DRAIN VALVE)
1. The OPEN (ON) time is adjustable from 0.5 sec to 10 sec. Drains are set at factory to open for 6
sec. When drain opens the on light will light
2. The CLOSED (OFF) time is adjustable 0.5 min to 45 min. Drains are set at factory to stay closed
for 10 min. When drain is closed the off light will light.
You may increase or decrease this based on moisture levels in the air.
Push the TEST button to manually open the drain valve.
HOW TO MAKE MINOR REFRIGERANT SUCTION PRESSURE ADJUSTMENTS.
1. Keep dryer running under a no load by turning off or bypassing the compressed air.
2. Remove dryer top and locate the Hot Gas Bypass Valve.
3. Remove cap on Hot Gas Bypass Valve and using an allen wrench turn valve counter clockwise
to decrease the suction pressure and clockwise to increase the suction pressure. Make ½ turn
adjustments and wait 2 to 3 minutes for suction pressure to stabilize. Make more adjustments if
needed.
(Minor Pressure Adjustments not covered under warranty.)
MHT 60 & MHT 130
MHT 25 & MHT 40
9