Electrical Box

6. Electrical Box
Warning
Step
1
Remove the screw,
then the drip proof
plate.
2
Cut the clamp.
3
Pull out the indoor heat
exchanger thermistor.
4
Remove the screw of
the earth/ground wire.
5
Remove the screw of
the wire fixture.
6
Remove the 4 screws
of the connecting wires.
8
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Indoor heat exchanger thermistor
Earth/ground wire
Drip proof plate
(R2771)
(R6707)
The position of the indoor
heat exchanger thermistor
varies depending on the
model.
Connecting
wire
Be careful not to lose the clip
of the thermistor.
Wire fixture
Clip
(R19204)
Si041254EE
Points
(R11234)
Removal Procedure