DSC PowerSeries PC1864 Руководство по установке - Страница 8

Просмотреть онлайн или скачать pdf Руководство по установке для Система безопасности DSC PowerSeries PC1864. DSC PowerSeries PC1864 13 страниц. System enhancement module
Также для DSC PowerSeries PC1864: Руководство по установке (17 страниц), Руководство по установке (20 страниц), Руководство (18 страниц)

DSC PowerSeries PC1864 Руководство по установке

UL Listed Commercial and Residential Installations

The control panel model PC1616/PC1832/PC1864 has been tested and found in
compliance with the following standard:
UL1610 Central-Station Burglar-Alarm Units
UL365 Police Station Connected Burglar Alarm Units and Systems
UL1023 Household Burglar-Alarm System Units
UL985 Household Fire Warning System Units
UL1635 Digital Alarm Communicator System Units
ULC-S304-06 Signal Receiving Centre & Premise Burglar Alarm Control Units
ULC-S559-04 Equipment for Fire Signal Receiving Centres and Systems
ULC-S545-02 Residential Fire Warning System Control Units
ORD-C1023-1974 Household Burglar-Alarm System Units
This product has also been tested and found in compliance with the ANSI/SIA CP-01-
2000 Control Panel Standard - Features for False Alarm Reduction
This product is UL/ULC listed under the following categories:
AMCX/AMCXC Central Stations Alarm Units
APAW Police-station-connected Alarm Units
DAYRC Central Station Fire Alarm System Units
UTOU/UTOUC Control Units and Accessories, Household System Type
NBSX/NBSXC Household Burglar Alarm System Units
AMTB Control Panels, SIA False Alarm Reduction
The product is labeled with the UL and ULC listing marks along with the SIA CP-01
compliance statement (Also Classified in accordance with SIA-CP-01 Standard) as proof of
compliance with the above mentioned standards. For further information on this product's
listings please also refer to the official listing guides published at the UL web site
(www.ul.com) under Certifications Section or ULC web site (www.ulc.ca) under Online
Directories.
UL/ULC Installations Required Programming Options
• All burglary-type zones shall be configured with SEOL or DEOL configuration (refer to
section [013], option 1 shall be OFF)
• Use at least one Smoke Detector for Fire Installations (refer to section [001], fire zone shall
be programmed as type 08 (hardwired) or 88 (wireless))
• The entry delay shall not exceed 60 seconds (refer to section [005])
• The exit delay shall not exceed 120 seconds (refer to section [005])
• The minimum Bell Time-out is 4 minutes (refer to section [005])
For ULC Residential Fire Installations the minimum Bell Time-out is 5 min.
For UL Home Health Care Installations the minimum Bell Time-out is 5 min.
For UL Commercial Burglary Installations minimum Bell Time-out is 15 min.
• Temporal Three Fire Signal shall be enabled (Section [013], option 8 shall be ON)
• Arm/Disarm Bell Squawk shall be enabled when using wireless key WS4939 (refer to
section [014], option 1 shall be ON)
• A code will be required for bypassing (Section [015], option 5 shall be ON)
• Trouble beeps shall be enabled (Section [023], option 7 shall be ON)
• AC trouble indication LED shall be enabled (refer to Keypad Programming, section [075],
options 5 and 6 shall be ON )
• DACT Communicator shall be enabled for Supervising Station Monitoring (refer to
section [380], option 1 shall be ON).
The DACT communicator for this product has no line security.
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be ON)
The product shall be programmed to perform 5 (min.) to 10 (max.) attemptsfor
communication of an event to the supervising station. If unsuccessful, a Fail To
Communicate (FTC) trouble is generated.
• Test transmission cycle shall be set for monthly transmission (see Section [377])
For ULC Residential/Commercial installations set for daily test transmission
• UL Central Station and Police connect with standard or encrypted line security service
• The installation must use the T-Link TL250 or T-Link TL300 Internet/Intranet
communicator which communicates over LAN/WAN/Internet to the SG-System II or SG-
System II receivers.
• Polling time shall be 200 seconds and compromise detection time shall be 6 min.
• For Encrypted line security applications, the T-Link TL250 or TL300 shall have the
Encryption Key enabled (AES128 bit encryption algorithm is validated under NIST
Certificate No. 109).
UL Local, Central Station and Police Connect with No Line Security Service
• The installation shall use a Bell which is UL Listed for Mercantile local alarms (i.e.
AMSECO MBL10B with model AB-12 bell housing.
• The digital communicator shall be enabled
• The control panel shall be in the attack resistant enclosure DSC Model CMC-1 or
PC4050CAR
UL Home Health Care Signaling Equipment
• There must be at least two keypads, one of either one of the compatible keypads models
PK5500, PK5501, PK5508, PK5516
• Each system shall be programmed to activate an audible Trouble signal within 90 seconds
upon loss of microprocessor memory
PowerSeries PC1616/PC1832/PC1864 Installation Guide
ULC Central Station Fire and Burglary Monitoring Installations
• For installation requirements, levels of security, communication modules and
configurations (Refer to the ULC Installation Information Sheet, DSC #29002157)
• Use CSA/cUL approved transformer (hardwired connections for Fire Monitoring)
• All tamper circuits may be connected to the same zone
Programming
The notes in the programming sections describing the system configurations for UL/ULC
listed installations shall be implemented
Control of the Protected Premises
In order to have a UL certificated system the protected are is to be under the responsibility
of one ownership and management (i.e., one business under one name). This may be a group
of buildings attached or unattached with different addresses but under the responsibility of
someone having mutual interest. The person of the mutual interest is not the alarm-
installing company.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the person
operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
The local control unit and power supply must be protected in one of the following ways:
• The control unit and audible alarm device must be in a protected area which is armed 24
hours a day.
• Each partition must arm the area protecting the control unit and the audible alarm device
power supply. This may require duplicate protection armed by each partition. Access to
this protected area, without causing an alarm, will require that all partitions be disarmed.
• In all cases described above, the protected area for the control unit must be programmed as
not-bypassable.
Casual Users
The installer should caution the user(s) not to give system information (e.g. codes, bypass
methods, etc.) to casual users (baby-sitters or service people). Only the One-Time Use codes
shall be given to casual users.
User Information
The installer should advise the users and note in the User's Manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time
• Test system weekly
• The installer's code cannot arm or disarm the system
SIA False Alarm Reduction Installations
Minimum required system consists of one Control unit model PC1864 or PC1832 or
PC1616 and any one of the compatible listed keypads: PK5500, PK5501, PK5508, PK5516,
PKP-LCD, PKP-ICN. For a list of default values programmed when the unit is shipped and
for any other programming information refer to False Alarm Reduction.
The following optional subassembly modules also bear the SIA CP-01-2000 classification
and may be used if desired: PC5108 Zone Expander, PC5208 PGM Output Module, PC5204
Auxiliary Power Supply and PC5400 Serial Output Module.
CAUTION
• For SIA FAR installations use only modules/devices that are listed on this page
• Fire Alarm Verification feature (Auto Verified Fire Zone type [29]) is not supported on 2-
wire smoke detectors zones. This feature may be enabled for 4-wire smoke detectors only
The fire alarm delay is 60s.
• Call Waiting Cancel (Section [382], Option 4) feature on a non-Call Waiting line will
prevent successful communication to the supervising station.
• All smoke detectors on the system must be tested annually by conducting the Installer
Walk Test. Prior to exiting the walk test mode, a sensor reset must be conducted on the
system, [*][7][2] to reset all latching 4-wire smoke detectors. Please refer to the smoke
detector installation instructions on how to correctly test the detectors.
NOTES
• Programming at installation may be subordinate to other UL requirements for the intended
application
• Cross zones have the ability to individually protect the intended area (e.g. motion
detectors which overlap)
• Cross zoning is not recommended for line security Installations nor is to be implemented
on exit/entry zones.
• This control panel has a communication delay of 30 seconds. It can be removed, or
increased up to 45 seconds at the option of the end user by consulting with the installer.
• Do not duplicate any reporting codes. This applies to all communication formats other
than SIA or CID sending automatic programmed reporting codes.
• The security system shall be installed with the sounding device activated and the
communicator enabled for transmission using SIA or CID format.
The control panel model PC1864/PC1832/PC1616 has also been tested and found in
compliance with UL636 Standard for Holdup AlarmUnits and Syatems and is UL listed
under the ANET category when used in conjunction with the DSC Model WS4928 Holdup
switch and the compatible wireless receiber model DSCRF5132-433. For UL listed systems
containing the UL holdup switch, the Force fArm (bit 5) zone attribute for Holdup zone
(type 12) shall be enabled (ON).
- 8 -