DSC Classic PC1565 Краткое руководство - Страница 14
Просмотреть онлайн или скачать pdf Краткое руководство для Панель управления DSC Classic PC1565. DSC Classic PC1565 18 страниц. Security control panels
Power Up
correct; and check voltage at the far
end. Disconnect furthest item on
Keybus and work back measuring
voltage. The panel will provide around
550mA of current for powering
modules and detection devices.
Always keep this in mind when ex-
panding a system.
You may be using a wireless module
with the Classic PC1565. Always
repower the control panel after adding
them onto the system. You will also
need to enable supervision, [*][8]
[Engineer Code][902[. Wait one
minute then enter [903]. The added
modules should now be displayed.
Push the [#] key when you have
finished. If a unit is not displayed in
the [903], check all of the connec-
tions for the unit.
12
Initial Start Up
Clearing Troubles
If the orange "Trouble" LED is lit,
there is trouble on the system. To
view, press [*][2].
The trouble condition will be dis-
played on the LCD keypad. Scroll
through the display using the [<][>]
keys to see if more than one trouble
condition is present.
On the LED keypads, the trouble
condition will be indicated by a lit LED
zone.
NOTE: Zone 1 LED gives a further
sub-menu of troubles. Therefore, if [1]
is lit, push [1] again for specific
information on the trouble condition.
Keypad Display After Pressing [*][2]
LED Lit LCD Display
[2]
AC Failure
AC no longer supplied to control
unit. To inhibit reporting of short
power-out durations, programme
delay in section [370].
[3]
Telephone Line Trouble
Telephone connection to control
panel reporting problem with
connection. Check telephone line
voltage and connection. Power
down with phone line connected.
Clearing Troubles
Features
21