DSC LE4020CF Руководство по установке - Страница 3
Просмотреть онлайн или скачать pdf Руководство по установке для Сотовый телефон DSC LE4020CF. DSC LE4020CF 8 страниц. Lte / 3g cellular alarm communicator
This manual covers two communicator models, the LE4020 and the LE4020(CF). They are referred to
throughout this manual as LE4020/LE4020CF unless otherwise indicated.
This LE4020/LE4020CF manages transmissions to a central station and can simulate the landline in the
event of trouble (e.g., landline down) or even substitute the landline completely in areas where the 3G or
2G cellular service is provided and a landline is not available.
By connecting a to a control panel's standard PSTN interface, telephone-based Contact ID or SIA signals are
decoded and seamlessly routed through the LTE or 3G network to any of the compatible receiver options.
The LE4020/LE4020CF are wireless communicators for UL commercial fire and/or burglary applications.
Both models send alarm system information to a Sur-Gard System I-IP, II, III, IV or 5 receiver. The
LE4020/LE4020CF uses the LTE or 3G wireless network. The LE4020/LE4020CF can be used with
UL/ULC Listed compatible control units, as indicated in the manufacturer's installation instructions.
NOTE: These communicators are designed to work with the Contact ID communication format as described
in the SIA DC-05 standard and the SIA DC-03 standard for 300 baud. Before completing the field install-
ation of the alarm monitoring system please ensure communication with the supervising central station is
successful by sending several events and getting confirmation that they have been received.
Features
Dual-band UMTS/HSPA; Penta-Band LTE (LE4020)
l
Advanced Carrier Selection
l
Bi-color Wireless Signal Strength Indicator
l
LTE or 3G Internet communication with Sur-Gard SG-System I-IP / II / III / IV / 5
l
Compatible with listed alarm control panels that have an integrated DACT and support a 4-digit or 10-
l
digit Contact ID communication format as described in SIA DC-05 Standard and the SIA DC-03 standard
for 300 baud. Example of suitable compatible alarm panels:
DSC Models PC1864, PC1832, PC1616, PC4020. For LE4010, the following alarm panels are also com-
patible: HS2128, HS2064, HS2032, HS2016
Panel Transmission Monitoring for up to four phone numbers
l
Simulates landline
l
Switches automatically to the LTE or 3G (LE4020CF) network in the event of landline trouble (e.g., line
l
down)
Four Programmable (NO/NC/SEOL) Inputs
l
Contains one 12V - 7 Ah battery
l
12V 1.2/4/7Ah battery (optional, not included)
l
Case Tamper Input
l
Landline overvoltage protection
l
Four Programmable Outputs
l
DLS support for status, firmware updates and remote debug enable
l
Remote Firmware Upgrade
l
Remote Diagnostics
l
Panel Format Detection
l
SMS Command and Control
l
Phone number call direction
l
Easy enrollment with C24 Communications via web or mobile interface
l
Technical Specifications
The input voltage to the LE4020/LE4020CF can be drawn from the UL/ULC Listed control panel or
provided by an external UL/ULC Listed power supply rated for the application (external power-limited
source).
NOTE: The power supply must be Class 2, Power Limited. For residential applications a suitable power
adaptor is model DSC ADP1310(W)-NAU or DSC ADP1320-NAU (for USA) and model DSC ADP1310(W)-
NA (for Canada).
Table 1: Ratings
Power Supply Ratings
Input Voltage:
Current Consumption
Average Current (standby
with PSTN connected):
Average Current (standby without
PSTN connected):
Transmission Current (no
battery):
* Plus any current drawn from the LE4020/LE4020CF AUX+ terminal. Each of the four PGM outputs can
be loaded up to 50 mA (max)
Introduction
9 Vdc to 28Vdc (use separately listed control panel or power supply)
oruse DSC ADP1310 (W)-NAx or ADP1320-NAx power adapter with
battery 12V 1.2/4/7Ah
3
40 mA*
55 mA*
225 mA*