Aube Technologies WZ45N Руководство по установке

Просмотреть онлайн или скачать pdf Руководство по установке для Переключатель Aube Technologies WZ45N. Aube Technologies WZ45N 2 страницы. Aube technologies inc. on/off switching electric heating relay installation guide

Aube Technologies WZ45N Руководство по установке
Application
The RC840 Electric Heating Relay is designed to control a line
voltage resistive load from a 24 V control signal.
The RC840 operates silently and can be installed in bedrooms, living
rooms, or any other occupied area without disturbing occupants. On
a call for heat, the relay is immediately activated; there is no delay.
This increases temperature control and comfort.
NOTE:
Not recommended for fast-cycling modulated regulation. For fast-
cycling heating equipment, It is recommended to use the RT850 or RT850T
(integrated 24 V transformer) Solid State Relay.
I
Installation
The RC840 must be installed in an area where the temperature is
between -4°F and 140°F (-20°C and 60°C).
The RC840 can be installed on the side of an electrical box or a
distribution panel or inside the wiring compartment of an electric
baseboard.
On the side of
an electrical box
All wiring must comply with national and local electrical code
regulations.
Installation should be carried out by an electrician.
Disconnect power supply before installing the relay to prevent
electrical shock.
Secure relay to the mounting surface using the two mounting
brackets. Use the supplied lock nut to secure the relay to the
junction box.
Wire the relay and connect according to typical wiring diagrams
(refer to figures 1, 2 and 3).
Once mounting and wiring have been completed, return power
to the heating system and test the installation.
Increase the thermostat temperature to activate the relay. Allow
system operation long enough to proof installation. Once
installation has been proofed, set temperature to normal
setpoint.
RC840
For proper installation, use
a screw and a washer.
Inside the wiring compartment
of a baseboard
1.
Typical Wiring Diagrams
Junction box
2.
You must provide an overload protection and disconnect as required.
Figure 1 :
Connection to a 2-wire low voltage thermostat using a 24 V
Junction box
You must provide an overload protection and disconnect as required.
Figure 2 :
Connection to a 3-wire low voltage thermostat using a 24 V
Junction box
Load
Junction box
Load
You must provide an overload protection and disconnect as required.
Transformer VA output = RC840 Quantity x 1.2 VA
Figure 3 :
Connection to a 2-wire low voltage thermostat using a 24 V
external transformer and multiple relays

Installation Guide

On/Off Switching Electric Heating Relay
External 24V
transformer
Black
Red
Load
external transformer
External 24V
transformer
Black
Red
Load
external transformer
Black
Red
Black
Red
400-276-000-C
17/1/07
RC840
3.
Low-voltage
2-wire
thermostat
Low-voltage
3-wire
thermostat
Low-voltage
2-wire
thermostat
External 24V
transformer
1/2