Auber SYL-2352P Руководство по эксплуатации
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Контроллер температуры Auber SYL-2352P. Auber SYL-2352P 8 страниц. Pid temperature controller
AUBER INSTRUMENTS
Instruction Manual
SYL-2342, SYL-2352 PID TEMPERATURE CONTROLLER
Caution
This controller is intended to control equipment under normal operating
conditions. If failure or malfunction of the controller may lead to abnormal
operating conditions that may result in personal injury or damage to the
equipment or other property, devices (limit or safety controls) or systems
(alarm or supervisory) intended to warn of or protect against failure or
malfunction of the controller must be incorporated into and maintained as
part of the control system.
Installing the rubber gasket supplied will protect the controller front panel
from dust and water splash (IP54 rating). Additional protection is needed
for higher IP rating.
This controller carries a 90-day warranty. This warranty is limited to the
controller only.
1. Specification
Thermocouple(TC): K, E, S, N, J, T, B, WRe5/26
RTD(Resistance temperature detector): Pt100, Cu50
DC Voltage: 0~5V, 1~5V, 0~1V,
Input type
-100~100mV, -20~20mV, -5~5V, 0.2~1V.
DC current : 0~10mA, 1~20mA, 4~20mA. (use external
shunt resistor for higher current)
Input range
Please see section 4.7 for detail.
±0.2% Full scale: RTD, linear voltage, linear current and
thermocouple input with ice point compensation or Cu50
copper compensation.
0.2% Full scale or ±2 ºC: thermocouple input with internal
Accuracy
automatic compensation.
Note: for thermocouple B, the measurement accuracy of ±
0.2% can only be guaranteed when input range is between
600~1800 ºC.
Response time
≤ 0.5s (when FILt=0)
Display resolution
1 °C, 1 °F; or 0.1 °C
Fuzzy logic enhanced PID control
Control mode
On-off control
Manual control
Relay contact (NO): 250VAC/7A, 120V/10A, 24VDC/10A
Output mode
SSR voltage output: 12VDC/30mA
Alarm output
Relay contact. 250VAC/1A, 120VAC/3A, 24V/3A
Process high alarm, process low alarm, deviation high
Alarm function
alarm, and deviation low alarm
Manual function
Automatic/Manual bumpless transfer
Power supply
85~260VAC/50~60Hz
Power consumption ≤5 Watt
Ambient temperature 0~50ºC, 32~122ºF
Dimension
48 x 48 x100 mm (WxHxD)
Mounting cutout
45 x 45 mm
2011.02
INSTRUCTION MANUAL
Version 4.4
2. Available Configurations
Table 1. Controller models
Model
SYL-2342
SYL-2352
SYL-2342P
SYL-2352P
All the models listed in table 1 are 1/16 DIN size with dual-alarm outputs.
3. Terminal Wiring
Model SYL-2342, SYL-2342P
+
+
RTD
R
mA
V
R
W
3.1 Sensor connection
Please refer to table 3 for the input sensor type (Sn) setting codes. The initial
setting for input is for a K type thermocouple. Set Sn to the right sensor code
if another sensor type is used.
3.1.1 Thermocouple
The thermocouple should be connected to terminals 4 and 5. Make sure that
the polarity is correct. There are two commonly used color codes for the K
type thermocouple. US color code uses yellow (positive) and red (negative).
Imported DIN color code uses red (positive) and green/blue (negative). The
temperature reading will decrease as temperature increases if the connection
is reversed.
When using ungrounded thermocouple that is in touch with a large
conductive subject, the electromagnetic field picked up by the sensor tip
might be too large for the controller to handle, the temperature display will
change erratically. In that case, connecting the shield of thermocouple to
terminal 5 (circuit ground of the controller) might solve the problem. Another
option is to connect the conductive subject to terminal 5.
3.1.2 RTD sensor
For a three-wire RTD with standard DIN color code, the two red wires should
be connected to the terminals 3 and 4. The white wire should be connected
to terminal 5. For a two-wire RTD, the wires should be connected to terminals
4 and 5. Jump a wire between terminals 3 and 4. Set controller input type, Sn
to 21.
3.1.3 Linear input (V or mA)
Voltage and mA current signal inputs should be connected between terminals
2 and 5. Terminal 2 is positive.
3.2 Power to the controller
The power cables should be connected to terminals 9 and 10. Polarity does
not matter. It can be powered by 85- 2 6 0 V A C power source. N e i t h e r a
transformer nor jumper is needed to wire it up. For the sake of consistency
with the wiring example described later, we suggest you connect the hot wire
to terminal 9 and neutral to 10.
WWW.AUBERINS.COM
Control output
Relay contact output
SSR control output
Relay contact output
SSR control output
Model SYL-2352, SYL-2352P
AL1
AL2
1
13 14
6
2
7
Out
+
3
8
mA
V
4
9
AC
85~260V
5
10
TC
Figure 1. Wiring diagram
Ramp/soak option
No
No
Yes
Yes
AL1
AL2
1
13 14
6
+
+
2
7
SSR
RTD
3
8
-
R
4
9
AC
R
85~260V
5
10
W
TC
P1/8