DAN DRYER 244 Turbo Руководство по техническому обслуживанию и эксплуатации - Страница 3
Просмотреть онлайн или скачать pdf Руководство по техническому обслуживанию и эксплуатации для Сушилка DAN DRYER 244 Turbo. DAN DRYER 244 Turbo 12 страниц.
Reference
Version
244-ENG
09-01-2018
Installation and connection:
To protect the user against electric shock, it is important that the hand dryer is connected to the earth wire.
For fixed installation, connect via circuit breaker.
1. Remove transport protection block prior to
installation.
2. Remove the two cover screws at the bottom of
the cover using the supplied special Allen key.
Carefully remove the housing from the base
plate.
Remove the
cover screws
3. Attach the base plate to the wall using
appropriate screws in the four mounting
holes. Wiring can be hidden behind the
machine or may alternatively be fed through
the bottom of the cover.
Hole for wall
mounting
screw
Hole for wall
mounting
screw
DAN DRYER A/S • Tåsingevej 2 • DK-8940 Randers SV • Tel: +45 86 41 57 11 • Email: [email protected]
244 DAN DRYER Turbo (with nozzle)
Maintenance and service manual
Transport
protection block
Do not lift the
hand dryer by
the electrical
parts during
installation.
Remove the
cover screws
Hole for wall
mounting
screw
Hole for
hidden wiring
Hole for wall
mounting
screw
Cut-out for
wiring through
the bottom
Document
4. Connect wires as follows:
A. Connect the live wire (red or brown) to the
terminal block marked "L".
B. Connect the neutral wire (blue or black) to
the terminal block marked "N".
C. Connect the green and yellow earth wire to
the screw marked "
5. Remount the cover using the two cover
screws at the bottom of the cover and
test run the hand dryer.
If the machine is mounted in an enclosed
cabinet, it is important to be aware of the
following requirements:
The turbo hand dryer sucks a large amount of air
during operation. It is therefore important that the
cabinet/housing has ventilation holes of at least
35 cm2 for each hand dryer.
If the hand dryer is installed in an enclosed cabinet
it is important that there is enough space to
remove the hand dryer's cover so the machine is
easily accessible for cleaning or servicing.
Lang.
Page
ENG
3 of 12
".
Total area of ventilation
holes must be at least
35 cm
2
per hand dryer.
If the cabinet has a fixed
front plate, there must
be at least 200 mm
space to dismantle and
remove the hand dryer's
cover.