Anywire B284SB-01-1KPLP30 Руководство - Страница 14

Просмотреть онлайн или скачать pdf Руководство для Аксессуары Anywire B284SB-01-1KPLP30. Anywire B284SB-01-1KPLP30 16 страниц.

[Equipment Parameters and Their Settings]
Equipment
Variable
parameter
【1】
0
Alarm bit disabled
Alarm bit
100
Alarm bit enabled
【2】
Upper limit setting of pressure detection
Input 0 upper
0 to 1000
input 0
limit value
【3】
Lower limit setting of pressure detection
0 to 1000
Input 0 lower
input 0
limit value
【4】
Input 1 upper
Upper limit setting of pressure detection
0 to 1000
limit value
input 1
*
For input 2 points
type only
【5】
Input 1 lower
Lower limit setting of pressure detection
0 to 1000
limit value
input 1
*
For input 2 points
type only
【8】
0
Hysteresis mode
Operation mode
*
For input 1 point
1
Window comparator mode
type
【8】
0
Input 0: Hysteresis mode, Input 1: Hysteresis mode
Operation mode
*
For input 2 points
Input 0: Window comparator mode,
1
type
Input 1: Hysteresis mode
Input 0: Hysteresis mode,
2
Input 1: Window comparator mode
Input 0: Window comparator mode,
3
Input 1: Window comparator mode
【9】
Hysteresis mode: Positive logic
0
Input logic
Window comparator mode: Positive logic
*
For input 1 point
type
Hysteresis mode: Negative logic
1
Window comparator mode: Negative logic
【9】
Hysteresis mode: Positive logic
0
Input logic
Window comparator mode: Positive logic
*
For input 2 points
type
Hysteresis mode/Input 0: Negative logic
Hysteresis mode/Input 1: Positive logic
1
Window comparator mode/Input 0: Negative logic
Window comparator mode/Input 1: Positive logic
Hysteresis mode/Input 0: Positive logic
Hysteresis mode/Input 1: Negative logic
2
Window comparator mode/Input 0: Positive logic
Window comparator mode/Input 1: Negative logic
Hysteresis mode: Negative logic
3
Window comparator mode: Negative logic
【10】
Setting a time required to turn ON or OFF
0 to 255
Input response
input
time
【11】
Setting a monitoring time for alarm
3 to 255
Alarm
judgement
monitoring time
【12】
Setting an upper limit value for alarm
0 to 1000
Alarm upper
judgment
limit value
【14】
Setting a lower limit value for alarm
Alarm lower
0 to 1000
judgment
limit value
【15】
0
Normal use
Zero correction
1
Execution of zero correction
command
Factory-set
Description
variable
0
600
400
600
400
0
0
1
50
1000
0
0
-B284SB0*1K**P30 14/16-
[Specifications]
■General specifications
Operating ambient temperature/humidity
Storing ambient temperature/humidity
Vibration resistance
Shock resistance
Operating atmosphere
Operating altitude*
1
Pollution level*
2
*1 Do not use or store AnyWireASLINK devices in an environment where the pressure exceeds
the atmospheric pressure at an altitude of 0 meters. Doing so may result in malfunction.
*2 "Pollution level" is an index that indicates the degree of occurrence of conductive substances
in the environment where the device is used.
Pollution level 2 means the occurrence of only pollution by non-conductive substances.
In such an environment, however, electrical conduction could occur due to accidental
condensation.
■Transmission specifications
Service power supply
24V DC +15% to -10% (21.6 to 27.6V DC)
voltage
with a ripple of 0.5Vp-p or less
DC power supply superimposed total
Transmission method
frame/cyclic method
Synchronization method
Frame/bit synchronization method
AnyWireASLINK protocol
Transmission procedure
Connection mode
Bus type (Multi-drop method, T-branch
method, Tree branch method)
Number of connection
Number of bit points:
points*
512 points max. (IN: 256 bits, OUT: 256 bits)
3
Number of word points:
1024 words max.
(IN: 512 words, OUT: 512 words)
Number of connection units
Up to 128 units
Detection of transmission line disconnection,
RAS function
transmission line short-circuit, transmission
power supply voltage drop, and
duplicated/unregistered ID
*3 The number differs depending on the master unit. Be sure to refer to the manual of the
master unit for the number.
■Individual specifications
B284SB-01-1K□□P30
Number of
occupied points
B284SB-02-1K□□P30
Response time*
5
10ms max.
Detection functions
Slave unit voltage drop (DP-DN voltage drop)
Sensing level drop
Current consumption
Transmission side (DP-DN): 20.0mA
Weight
25g
Protection rating
IP40
Pipe connection
M5 female thread
bore diameter
B284SB-01-1KPP30
Withstand pressure
B284SB-02-1KPP30
B284SB-01-1KNP30
B284SB-02-1KNP30
B284SB-01-1KLP30
B284SB-02-1KLP30
B284SB-01-1KPLP30
B284SB-02-1KPLP30
Repeatability
±0.5% F.S.
Temperature characteristic
±2.5% F.S.
*4 When alarm bit is enabled
*5 Indicates the internal processing time of this unit.
For signal of the bit information area, the maximum transmission delay time is defined as
"this time + bit transmission cycle time × 2."
For signal of the word information area, the maximum transmission delay time is defined as
"this time + word transmission cycle time."
0 – +55°C, 10 – 90%RH No condensation
-25 – +75°C, 10 – 90%RH No condensation
Based on JIS B 3502 and IEC 61131-2
Based on JIS B 3502 and IEC 61131-2
No corrosive gas
0 to 2000m
2 or less
Bit input: 1 or 2 points
(Input 1 point + Alarm bit 1 point*
Bit input: 2 or 3 points
(Input 2 points + Alarm bit 1 point*
1500kPa
1500kPa
200kPa
200kPa
200kPa
200kPa
200kPa
200kPa
)
4
4
)