Anywire B284SB-01-1KPLP30 Руководство - Страница 3
Просмотреть онлайн или скачать pdf Руководство для Аксессуары Anywire B284SB-01-1KPLP30. Anywire B284SB-01-1KPLP30 16 страниц.
[Included in the Package]
Sensor body ... 1
Transmission line connection cable (300mm) ... 1
Panel mounting adaptor ... 1
*Prepare a metal bracket separately, if required.
[Name of Each Part]
Pressure display
L IN
K
Setting port
Transmission line
connector
Pressurizing port
(M5 female thread)
Mounting screw
hole (M3)
Transmission line
connection cable
A L
M
IN
M P
Lot label
0
a
IN
1
Input indicator
ALM indicator
LINK indicator
DN (Black)
DP (Red)
-B284SB0*1K**P30 3/16-
[How to Connect AnyWireASLINK]
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending
on the load current. If the load current is small, using a two-wire (non-isolated) terminal
allows for achieving simplified wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of
connections, hybridization with a four-wire (isolated) terminal, which supports local
power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving
using an external power supply.
[System Configuration Example]
■Connection with 2-wire (non-isolated) terminals only
Red:
Red: DP
DP
AnyWireASLINK
master
Black:
Black: DN
DN
Red: DP
24V DC*
Black: DN
* Make sure to use a
24V DC stabilized
power supply for the
power supply to be
connected.
Red: DP
* When complying with the
UL Standard, make sure
Black: DN
to use a 24V DC
stabilized power supply of
"NEC Class 2 Output."
Red: DP
Black: DN
Red: DP
Black: DN
General-purpose
cabtyre cable
Dedicated flat cable
1.25mm
2
(2-wire)
2P link connector is
convenient for
branching.
The sum of the
portions of DP, DN is
the total line length.
Black: DN
Red: DP
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
■ R elationship between the size and length of
the transmission line and the supply current (Table 1)
Supply current on the transmission line (DP, DN)
Size of
the transmission
Total length:
line (DP, DN)
50m or less
1.25mm
MAX 2A
2
0.75mm
MAX 1.2A
2
0.5mm
MAX 0.8A
2
- Refer to Table 1 so that the size and length of the
!
CAUTION
transmission line and the allowable supply current lie within
an appropriate range.
- Connect the same symbols (DP, DN) correctly between the AnyWireASLINK
master unit and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the "total line length."
- Connect the terminator (with polarity) on the transmission line terminal farthest
from the AnyWireASLINK master unit.
2 points
2 points
1 point
1 point
16 points
2 points
Black: DN
The branching
2 points
has no limitation.
Red: DP
2 points
Red: DP
Total length: Over 50m,
Total length: Over 100m,
no longer than 100m
no longer than 200m
MAX 1A
MAX 0.5A
MAX 0.6A
MAX 0.3A
MAX 0.4A
MAX 0.2A
Black: DN
2 points