Fault message
In an error situation the LED's on the front will flash and the alarm relay
will be activated. If you push the top button in this situation you can see
the alarm report in the display.
There are two kinds of error reports - it can either be an alarm occurring
during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error
occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:
Code / Alarm text via
Description
data communication
High temperature alarm
A1/--- High t.alarm
Low temperature alarm
A2/--- Low t. alarm
Door alarm
A4/--- Door alarm
The "o16" function is activated
A5/--- Max hold time
during a coordinated defrost
A13/--- High temp S6
Temperature alarm. High S6
A14/--- Low temp S6
Temperature alarm. Low S6
A15/--- DI1 alarm
DI1 alarm
A16/--- DI2 alarm
DI2 alarm
A45/--- Standby mode
Standby position (stopped
refrigeration via r12 or DI input)
A59/--- Case clean
Case cleaning. Signal from DI
input
A97/--- Comp. Safety
Compressor safety. Signal from
DI3 input
AA3/---High brine temp.
High brine temperature alarm
E1/--- Ctrl. error
Faults in the controller
E6/--- RTC error
Check clock
E25/--- S3 error
Error on S3 sensor
E26/--- S4 error
Error on S4 sensor
E27/--- S5 error
Error on S5 sensor
E28/--- S6 error
Error on S6 sensor
Error on S7 sensor
E50/--- S7 error
---/--- Max Def.Time
Defrost stopped based on
time instead of, as wanted, on
temperature
Data communication
The importance of individual alarms can be defined with a setting. The
setting must be carried out in the group "Alarm destinations"
Settings from
Settings from
System manager AK-SM
AKM (AKM destination)
High
1
Middle
2
Low
3
Log only
Disabled
AK-CC 460
Alarm
relay
groups
(P41)
1
2
8
16
1
2
8
8
-
-
8
8
32
32
4
4
4
4
4
16
Send via
Network
X
X
X
Instructions RI8SE202 © Danfoss 07/2017
Operating status
The controller goes through some regulating situ-
ations where it is just waiting for the next point
of the regulation. To make these "why is nothing
happening" situations visible, you can see an op-
erating status on the display. Push briefly (1s) the
upper button. If there is a status code, it will be
shown on the display. The individual status codes
have the following meanings:
Normal regulation
Waiting for end of the coordinated defrost
When the compressor is operating it must run for
at least x minutes.
When the compressor is stopped, it must remain
stopped for at least x minutes.
The evaporator drips off and waits for the time to
run out
Refrigeration stopped by main switch. Either with
r12 or a DI-input
Refrigeration stopped by thermostat
Defrost sequence. Defrost in progress
Defrost sequence. Fan delay — water attaches to
the evaporator
Refrigeration stopped due to open ON input or
stopped regulation
Door is open. DI input is open
Melt function in progress. Refrigeration is inter-
rupted
Modulating thermostat control
Emergency cooling due to sensor error *)
Manual control of outputs
Case cleaning
Delay on outputs during start-up
Case shut down
Other displays:
The defrost temperature cannot be displayed.
There is stop based on time
Defrost in progress / First cooling after defrost
Password required. Set password
Regulation is stopped via main switch
*) Emergency cooling will take effect when there is lack of signal from a
defined S3 or S4 sensor. The regulation will continue with a registered
average cutin frequency. There are two registered values – one for day
operation and one for night operation.
(Measure-
ment)
Ctrl. state:
(Shown in
all menu
displays)
S0
0
S1
1
S2
2
S3
3
S4
4
S10
10
S11
11
S14
14
S15
15
S16
16
S17
17
S18
18
S19
19
S20
20
S25
25
S29
29
S32
32
S45
45
non
-d-
PS
OFF
9