Danfoss AK-CH 650 Руководство по эксплуатации - Страница 6
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Контроллер Danfoss AK-CH 650. Danfoss AK-CH 650 15 страниц. Capacity controller for water chiller
--Zone delay s
Kp S4
Night offset K
Tref S3 offset
K1 S3 offset
Max.Reference °C
Min.Reference °C
VSD Min. speed Hz
VSD Start speed Hz
VSD Max. speed Hz
Load shed limit 1
Load shed limit 2
Override limit Po
Override delay 1 min
Override delay 2 min
Po pump down limit °C
Initial start time
1 comp. start delay
Extra cooling mode
Extra cooling offset
Extra cooling delay
Extra cooling init d.
Suction compressor status
Measurements
AK error
Comp. Ctrl. temp.
S4 Cold brine supply
S3 Cold brine return
P0 °C
Comp. ctrl. Ref. °C
Compressor cap. %
Request Comp. Cap %
Cond. ctrl. temp °C
S7 warm brine °C
Pc °C
Cond. ctrl. ref. °C
Cond. cap. %
Request Cond. cap %
VSD 1 safety
VSD 2 safety
Comp. 1 Status
6
Time delay between step cut-outs in the regulation band under the "-Zone band"
Set in seconds.
Amplification factor for P0 regulation
Displacement value for suction pressure in connection with an active night
setback signal (set in Kelvin)
Reference temperature for the temperature signal S3, i.e. when = Tref, there is no
displacement of the reference.
Displacement of the reference for the charge temperature S4 on an increase in S3
temperature in relation to "Tref S3 offset" of 1°C (K1 = 0 gives no displacement)
Max. permissible suction pressure reference
Min. permissible suction pressure reference
Minimum allowed speed before stop of Variable Speed drive (Low load condition)
Minimum speed for start of Variable speed drive (Must be set higher than
"VSD Min. Speed Hz")
Highest permissible speed for the compressor motor
Set max capacity limit for load shed input 1
Set max capacity limit for load shed input 2
Set max load shedding override limit for suction pressure Po
Override delay for load shed limit 1. If the suction pressure exceeds
"Override limit Po" during load shedding and the set delay has expired, the load shed
limit 1 will be cancelled
Override delay for load shed limit 2. If the suction pressure exceeds
"Override limit Po" during load shedding and the set delay has expired, the load shed
limit 2 will be cancelled
Set the actual pump down limit for the last compressor
The time after start-up where the cut-in capacity is limited to the first compressor step.
On new start the start of the first compressor is delayed by the set delay time so that the
brine pumps can bring the brine up to speed before start of the first compressor.
A relay is reserved and it will be activated if the brine temperature is higher than
desired.
Set the value (K above the reference) where the relay is to activated
Delay time before the relay can be active. The time applies during normal regulation
Delay time before the relay can be active. The time applies during cooling after start-up
and after defrosting.
When "ON", the controller is in alarm condition.
Actual temperature for compressor control
Actual cold brine supply temperature measured with S4 temp. sensor
Actual cold brine return temperature measured with S3 temp. sensor
Suction pressure in °C. (Measured with the pressure transmitter)
Actual reference temperature for compressor control
Cut-in compressor capacity in % (of total capacity)
Reference for compressor capacity (deviations may be due to time delays)
Actual temperature for control sensor (Pc or S7)
Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cut-in condenser capacity in % (of total capacity)
Reference for condenser capacity
Status on safety input for variable speed controller on compressor 1
ON: Alarm
OFF: No alarm
Status on safety input for variable speed controller on compressor 2
ON: Alarm
OFF: No alarm
0: Power up
1: Stopped
2: Manual
3: Alarm
4: Restart
5: Standby
10: Full loaded
11: Running
Service Guide
RC8BV402 © Danfoss 2016-02
Controller has been powered up/Compressor is not used
Compressor hat been stopped
Compressor capacity is controlled manually
Compressor is in alarm condition (cut out on safety)
Compressor is waiting for elapse of "Recycle time"
Compressor is ready to start
All capacity cutin
Capacity control is running
AK-CH 650 Version 2.0x