AK-SC255

Won't Power up

Receiving error message(s)

Database History isn't available or
is lost

Clock doesn't work

EDF Message

For Danfoss Technical Support call +1-410-931-8716.
6
Troubleshooting Guide
Check for incoming power at MK1 connector.
Check fuse at F1 (Fig. 6).
Check for input power at the base of the power supply.
Check for 5vdc between MH5 and MH6 on the 255PROGBD (the yellow 5v in
LED and the green 5v out should be lit.
Contact Danfoss Technical Support to resolve source and resolution of your
particular error messages.
Insure that the battery jumper at JP5 on the base board (Fig. 7) is set on the
right two pins (this is the enabled position).
Check to see that there is a valid database with history configured.
Check to see that history status is Collecting and not Suspended
See if you can access history retrieval via the keypad via the AKA65
If you can still not access history contact Danfoss Technical Support for further
options.
Insure that the battery jumper at JP5 on the base board (see Fig. 7) is set on
the right two pins (this is the enabled position).
Now try resetting the correct date and time. Observe this new time for several
minutes.
If, after several minutes, the clock appears to be correct you have most likely
corrected the perceived problem.
If, after a short time, the date returns to 01/31/95 and the clock to 00:00:00...
call Danfoss Technical Support for further assistance.
The most common EDF message is one saying "Could not Load..., " this usually
implies that the necessary EDF was not in the correct directory or folder. Make
sure the EDF mentioned in the error message is in your list of EDF's.
Remember, after loading EDF's or a Device List you must reset the AK-SC255.
If your problem is still not resolved, call Danfoss Technical Support for
assistance..
USCO.EI.RF0.D1.22 / 521U0152
1.0 Amp 250V
fuse on the "hot leg"
of input power
Figure 6
Figure 7