cashco 764P Руководство по установке, эксплуатации и техническому обслуживанию - Страница 8

Просмотреть онлайн или скачать pdf Руководство по установке, эксплуатации и техническому обслуживанию для Контроллер cashco 764P. cashco 764P 14 страниц. Pneumatic pressure controllers

VI. SHOP CALIBRATION
1. Install a 1/4" pipe plug in the "OUTPUT" port of
unit.
2. Provide an 18 psig (1.2 Barg) IAS to the proper
port as determined by Table 1, Section II.
3. Leave PB as set in Section V.C.13. If this
setting is unknown, rotate the PB needle valve
(3) CW until seated. Rotate needle valve (3)
CCW until "indented matchmarks" align; this is
approximately/8–1/4 of a revolution.
4.1. Provide a known pressure (compressed nitrogen,
etc.) equal to the desired setpoint to the di a phragm
"PRO CESS" connection for the 764P.
4.2. For the 764PD, place a known static pressure
equal to the desired differential pressure setpoint to
the "HIGH" process connection; leave the "LOW"
process connection vented to at mo sphere.
VII.
TROUBLE SHOOTING GUIDE
1. No controller response
Possible Cause
A. No air supply.
B. Improper action; port "A" or "B"
connections reversed.
C. Check process isolation valve and line to
see if open and/or clear.
D. Improper pressure tap location.
E. PB needle valve is fully closed.
F. Adjusting Screw is outside of operating
window.
G. Ice formation.
H. Final element operation problem; i.e.
control valve, positioner, solenoid, etc.
8
SECTION VI
5.1. FOR DIRECT ACTION: If the output pressure
gauge is at/near 15 psig (1.03 Barg) increase the
setpoint by rotating the adjusting screw (2.3) CW
until the output decreases to 9 psig (0.62 Barg)
If the output pressure gauge is at/near 0 psig
(0.0 Barg) decrease the setpoint by rotating the
ad just ing screw (2.3) CCW until the output rises
to 9 psig (0.62 Barg).
5.2 FOR REVERSE ACTION: If the output pressure
gauge is at/near 15 psig (1.03 Barg) decrease
the setpoint by rotating the adjusting screw (2.3)
CCW until the output decreases to 9 psig (0.62
Barg).
If the output pressure gauge is at/near 0 psig
(0.0 Barg) increase the setpoint by rotating the
ad just ing screw (2.3) CW until the output rises
to 9 psig (0.62 Barg).
NOTE: If the unit cannot be shop calibrated to either
the upper or lower value of the stated range, refer
to statement in VII.7.A. for recommendation. Re peat
shop calibration.
SECTION VII
A1. Check to see if air is available at airset.
A2. Check to see if airset filter and/or dripwell is plugged.
B.
Reference Tables 1 & 2 herein for desired action and proper
port; reverse as required.
C1. Open block needle valve on process.
C2. Disconnect piping/tubing at both ends, blow to determine
if obstructed. Carefully blow needle valve to clear obstruction;
use caution commensurate with fluid handled in accordance
with Owner's procedures.
D. For relief applications, tapping is upstream; for reducing
applications tapping is downstream of the control valve.
E. Open at east to alignment of matchmarks on valve's screw
head and housing.
F. Reset Adjusting Screw length to be 5/16" out from nameplate.
G. Use dry air as an IAS medium in cold weather. Thaw as
necessary by use of air heater. Trace as necessary.
H. Reference instructions for operation of final element.
Remedy
IOM-764P / PD