Installation Instructions
Inrush Card Kit for D1h–D8h Drives
®
VLT
FC Series FC 102, FC 103, FC 202, FC 302
1.1 Description
The inrush card kit includes all parts required to install the
inrush card in D1h–D8h drives.
1.1.1 Kit Ordering Numbers
Number
Kit description
176F3159 Inrush card NO 110–315 kW 400 V (T5)
176F3417 Inrush card NO 75–400 kW 690 V (T7)
176F3517 Inrush card rugged NO 110–315 kW 400 V (T5)
176F3518 Inrush card rugged NO 75–400 kW 690 V (T7)
Table 1.1 Ordering Numbers for Inrush Card Kits
1.1.2 Items Supplied
The following items are included with the inrush card kits for
D1h–D8h drives.
Item
Inrush card
Standoff (for D1h/D3h/D5h/D6h drives only)
Installation instructions
Table 1.2 Items Supplied with Inrush Card Kit
1.2 Safety Information
Only qualified, Danfoss-authorized personnel are allowed to
install the parts described in these installation instructions.
Disassembly and reassembly of the drive must be done in
accordance with the corresponding service guide.
ELECTRICAL SHOCK HAZARD
®
VLT
connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
•
•
•
•
DISCHARGE TIME
Quantity
The drive contains DC-link capacitors, which can remain
1
charged even when the drive is not powered. High voltage
3
can be present even when the warning LED indicator lights
are off. Failure to wait the specified time after power has
1
been removed before performing service or repair work can
result in death or serious injury.
•
•
•
•
•
ELECTROSTATIC DISCHARGE
Follow proper ESD precautions to prevent damage to
sensitive components.
Danfoss A/S © 05/2018 All rights reserved.
WARNING
FC series drives contain dangerous voltages when
Only use qualified electricians for the installation.
Disconnect the drive from all power sources before
installation or service.
Treat the drive as live whenever the mains voltage
is connected.
Follow the guidelines in these instructions and local
electrical safety codes.
WARNING
Stop the motor.
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum waiting time is 20 minutes.
Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.
MI39A102