DANLERS EZ CESR Указания по установке - Страница 2
Просмотреть онлайн или скачать pdf Указания по установке для Переключатель DANLERS EZ CESR. DANLERS EZ CESR 2 страницы. Easyzapp ceiling flush mounted switches
Installation procedure
1. Please read these notes carefully before commencing work. In case of doubt
please consult a qualified electrician. Ensure wires and cables are securely held
within the connection terminals.
IMPORTANT: The EZ CESR Control Unit clock battery must be engaged (ON)
prior to installation by switching the RED dip switch (see diagram E) to the
DOWN position.
2. POSITIONING: The EZ CESR switch should be installed to achieve correct
coverage of the area, see diagram B. If the photocell override facility (enabled
via EasyZAPP app) is required, the switch must be located above an area where
daylight can give greater illumination than the artificial light. Avoid locating this
product where it is exposed to drafty conditions (exposed lobbies, open ceiling
voids or near fans) or near heat sources. To cover large areas PIRs should be
spaced in a 5 metre grid formation.
3. Disconnect the PIR from the circuit before performing insulation testing of the
wiring circuit.
4. Do not connect on a circuit with large inductive loads, as induced spikes may
cause false triggering or damage the PIR.
5. EZ CESR must be connected to the EasyZAPP Power Supply (CZPS) via the
EasyZAPP communication cable (telejack) provided, for wiring see diagrams C and
D.
NOTE: The use of non EasyZAPP connectors may damage the EZ CESR or CZPS
and will invalidate the warranty).
6. Knockout or drill the appropriate holes on the mounting plate for attaching the plate
to the ceiling or back box (if applicable). Feed telejack through the appropriate (side
or rear) entry hole. Screw the back mounting plate to the ceiling or back box via the
mounting holes. Push the telejacj connector into the sensor head terminal. Push the
sensor head onto the mounting plate and align the side clips with the slots on the
sensor heads.
Settings and calibration
ALL settings are adjusted by EasyZAPP App as detailed in the free to download
EasyZAPP App User Guide, including:
Timeout: Adjustable time lag from 10 seconds to 24 hours.
Brightness: Adjustable switching threshold, 30 to 1000 lux and inactive. EZ CESR
must be calibrated as instructed on the user guide manual.
Batch Configure: For configuring multiple EZ CESR controls with identical settings.
Name: For identifying individual controls.
Password: For security against accidental or malicious alteration.
Please visit www.danlers.co.uk to download the EasyZAPP user guide.
A: Mounting diagram
Knock out mounting
For telejack entry from
holes or pre-drill
above - knock out
pilot holes.
central mounting hole
B: Detection diagram
Strong detection zone
i.e. person moving arm
or walking towards PIR
up to 5m
up to 7m
C: Wiring diagram
Single EZ CESR
L
SL
L
N
100 - 260 VAC
50 / 60 Hz
load
N
D: Connector diagram
Several EZ CESR wired in parallel
L
L
L
L
IMPORTANT
N
N
N
Red dip switch (MUST be
SL
SL
SL
100-260 VAC
switched towards centre of control)
50 / 60 Hz
to engage clock battery ON
SL
L
N
L
Power Supply
N
Telejack connector
Clip telejack into the device
For side entry -
then join device to mounting
knock out side
plate via mounting clips
mounting hole
For optimum coverage
recommended
mounting height: 2.4 to 5m
Single EZ CESR
Secondary detection
L
SL
L
zone i.e. person
walking perpendicular
N
to PIR
100 - 260 VAC
50 / 60 Hz
N
D: Wiring diagram
Several EZ CESR wired in parallel
L
L
L
L
N
N
N
SL
SL
SL
100-260 VAC
50 / 60 Hz
N
Control Unit
load
ON
load
load