Programming Motor Power during Deceleration
The control unit allows you to programme the motor power to
which the deceleration phase will be carried out.
It is possible to choose between 6 different levels of power in
this way: every combination of lit LEDs corresponds to a level
according to the table above; in other words, starting from the
lowest LED ( LED AUT/ P-P ) and moving upwards, each LED
corresponds to a higher power level. Using the SEL key it is
possible to scroll through the different power levels; for every
selected power level, the highest respective LED will flash (for
example, if level 4 is selected the AUT/ P-P, CODE and CODE
PED LEDs light up steady, whereas the INB CMD. AP LED
flashes); press SET to confirm.
Level 3 is selected in the default configuration.
RESET :
To reset the default configuration of the control unit, press the
SEL and SET buttons simultaneously; all RED signal Leds will
switch on and then immediately off again.
DIAGNOSTICS :
Photocell Test :
Pagina 6 di 6
The control unit is designed for the connection of safety
devices that comply with point 5.1.1.6 of standard EN 12453.
With every operation cycle, it performs a test of the operating
photocells connected. If there is no connection and/or non
operation, the control unit does not enable gate motion, and
will visually report the failed test by simultaneously flashing all
of the LED signal lights flash. Once the photocells are running
correctly again, the control unit is ready for normal operation.
This ensures monitoring against failures, in compliance with EN
954-1, Category 2.
Control input test:
On each low voltage control input, the control unit uses a LED
signal to make the status readily known.
Operating logic: when a LED is on it means the input is closed,
when a LED is off it means the input is open.
LED MANAGEMENT :
After 3 minutes of inactivity in the programming procedure,
there is the automatic shutdown of
savings. A single press of the SEL or SET key, or a movement
command will activate the LED light up according to settings
programmed previously.
the Leds
for energy