Contemporary Controls BASRT-B Руководство по установке - Страница 18

Просмотреть онлайн или скачать pdf Руководство по установке для Сетевой маршрутизатор Contemporary Controls BASRT-B. Contemporary Controls BASRT-B 20 страниц. Bacnet/ip to ms/tp router

those passed by the router from BACnet/IP. The default value
usually provides good performance.
MS/TP Baud Rate
(Default Value = 38400)
The baud rate of the MS/TP network can be 9600, 19200, 38400
or 76800 bps. All MS/TP devices on the same MS/TP network
must use the same baud rate. On power up the router checks for
other masters; if finding none, it begins token passing — at which
point autobauding devices will adjust to the router's baud rate.
MS/TP Tolerance
(Default Selection = Strict)
This setting determines the degree to which interoperability with
devices is successful. The Lenient option is less efficient for
traffic flow but optimizes interoperability. A slight improvement
in performance will be realised by selecting the Strict setting.
TD071200-0IC
18