Apollo REACH WIRELESS RW1500-110APO Краткое руководство по эксплуатации

Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Морское оборудование Apollo REACH WIRELESS RW1500-110APO. Apollo REACH WIRELESS RW1500-110APO 4 страницы. Open-area wall sounder

Apollo REACH WIRELESS RW1500-110APO Краткое руководство по эксплуатации
REACH Wireless®
Open-Area Wall Sounder
Product overview
Product
Part No.
Digital Communication
Approvals
Product information
The RW1500-110APO and RW1500-120APO comprise of a
wireless addressable interface and conventional open-area
wall sounder that can be used as a stand-alone notification
device.
• Compatible only with REACH Wireless
• 16 tone pair settings (primary and secondary for alert
and evacuation), selectable via on-board DIL Switches
• Four Volume Settings
• Bi-directional wireless communication
• Dual channel redundancy
• Five year battery life
• Five year product warranty
36 Brookside Road, Havant
Hampshire, PO9 1JR, UK.
MANAGEMENT
MANAGEMENT
SYSTEMS
SYSTEMS
Assessed to ISO 9001:2015
Assessed to ISO 14001:2015
Cert/LPCB ref. 010
Cert/LPCB ref. 010 EMS
REACH Wireless Open-Area
Wall Sounder
RW1500-110APO (White Body)
RW1500-120APO (Red Body)
Apollo protocol compatibility is
handled via the Loop-Interface device,
RW1700-030APO.
See product for more detail.
Tel: +44 (0)23 9249 2412
Email: enquiries@apollo-fire.com
Fax: +44 (0)23 9249 2754
Web: www.apollo-fire.co.uk
PRODUCT
CT
CERTIFICATION
TION
© Apollo Fire Detectors Ltd 2022
Cert/LPCB ref. 010
Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24 V, 25°C and 50% RH unless otherwise stated.
Number of Tone Pairs
16 (see table 2)
Volume Levels
Four (see table 3)
Sound Output (Typical)
88 - 91 dBA (tone dependant)
Communication Range
100 m (in open space)
between Loop-Interface and
Devices
Field Device Radio Frequency
22 pairs
Channel Pairs
Radiated Power
14 dBm (25 mW)
Battery Type
2x VARTA CR123A Lithium 3 V,
1250mAh typical
Battery Lifespan
Five years in normal operation with
good signal strength (no dropped
messages)
Operating Temperature
-10°C to +55°C
Maximum Relative Humidity
95%
(non-condensing)
IP Rating
IP 35 (Type B Indoor Use)
Standards and approvals
EN54-3, EN54-25
Dimensions
126 mm diameter x 132 mm height
x 125 mm depth
Weight (including base and
350 g
batteries)
77 mm
65 mm
126 mm
132 mm
All information in this document is given in good faith but Apollo
Fire Detectors Ltd cannot be held responsible for any omissions
or errors. The company reserves the right to change the
specifications of products at any time and without prior notice.
PP5105/2022/Issue 1
Page 1 of 4
35 mm
30 mm
80 mm