TEST NO. 3
PURPOSE: To test leaking #2 shut-off valve
As previously mentioned, the above test is not accurate when the second shut-off valve is leaking . The following test will expose
a leaking shut-off valve .
1 .
Both shut-off valves should be open . Make sure all valves on test kit are closed . Connect the high "A" hose to test cock #2
and the low "B" hose to test cock #3 . Open test cock #2 and test cock #3 .
2 .
Open the high "A" valve and vent "C" valve to bleed air from high side of gauge . Open low "B" valve to bleed air from low side
of gauge . Close valves "A", "B" and "C" on test kit .
3 .
Connect the vent hose to test cock #4 . Open test cock #4 .
4 .
Close shut-off valve #2 . The differential gauge needle should read at least 1 .0 psid in order to pass .
5 .
Open the high "A" valve and vent "C" valve . This will put back pressure on check valve #2 .
6 .
Close test cock #2 .
NOTE: If gauge is steady, then shut-off valve #2 is holding tight. However, if gauge drops to zero psid, then shut-off valve #2 is leaking.
NOTE: If the gauge rises then the #2 shut-off valve is still leaking, but is under backpressure from the facility.