4EVAC IMPACT Руководство пользователя - Страница 4
Просмотреть онлайн или скачать pdf Руководство пользователя для Оборудование для обеспечения безопасности 4EVAC IMPACT. 4EVAC IMPACT 14 страниц. Controller
Также для 4EVAC IMPACT: Справочное руководство (8 страниц)
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
CONTROLLER user manual
EVAC
Indicates that the system is in the Voice Alarm state, where at least one zone in the system is occupied by
an emergency audio signal, i.e. a pre-recorded EVAC MESSAGE or LIVE EVAC, when a fireman mic is being
used.
OFF
RED continuous
GENERAL FAULT
Indicates that the system is in the FAULT state (general fault indicator), where at least one device in the
system is reporting a fault.
OFF
YELLOW continuous
YELLOW blinking
POWER SUPPLY FAULT
Indicates a power supply fault of the local Impact system, where at least one of following faults is reported
OFF
YELLOW blinking
YELLOW continuous
SYSTEM FAULT
Indicates a system fault of the Impact Controller, where:
-
a CPU or program execution is stopped or malfunctioning,
-
there is a corruption of storage memory containing config settings and audio files (SD card).
Where the system fault is caused by a CPU or memory fault, the Controller remains in its "safe state", where
critical functions (including audio transmission, reaction on control inputs, etc.) are stopped until the fault
is resolved.
OFF
YELLOW continuous
Author:
EVAC status is inactive (quiescent mode)
EVAC status is active
System is healthy
Local fault is detected
(failure of Impact controller or local AMP LINK amplifiers)
Remote fault is detected
(this Impact controller and amplifiers are healthy and another device in the
network is reporting fault state)
Power supply OK
Battery-related fault:
o
Loss of battery
o
Loss of charger
o
Battery resistance too high
o
Temperature fault
Mains fault
Firmware and settings OK
CPU / program fault
Page 4 of 14
DD