Datacom DFC-0115 Руководство - Страница 6

Просмотреть онлайн или скачать pdf Руководство для Контроллер Datacom DFC-0115. Datacom DFC-0115 8 страниц. Reactive power controller

Datacom DFC-0115 Руководство
DEFINITION
"t-dU"
Step switching
delay
When the unit
decides to switch
the step
configuration, it
continues
measurements
during this delay
and sets the new
step configuration
calculated at the
end of this delay.
"t-CL"
Step switching
protection delay
When the unit sets
a new step
configuration, all
step switching will
be disabled during
this timer.
"dCHr"
Discharge timer
This is the
common discharge
timer for all steps.
Any step swithed-
off, cannot be
switched on again
before expiration
of this timer.
MIN
STD MAX
1 sec
1 sec
2000
sec
0 sec
1 sec
2000
sec
3 sec
14
2000
sec
sec