pressure. This input must be properly connected for the correct operation of
the unit. If oil pressure is provided, the generator will not start and the oil
pressure alarm indicator will flash. However, if the oil pressure is removed, the
unit will resume normal operation.
24- EMERGENCY STOP INPUT: Emergency stop button is connected to this
input. The connection shall be made in order to give DC Supply (-) to the input
when the button is pushed. Pushing the STOP button on the unit's front panel
makes the same effect as the EMERGENCY STOP input. The generator will
not operate when the emergency stop signal is present. When the signal is
removed, the unit will resume normal operation. This input can also be used to
prevent externally the automatic operation of the generator. (for ex. by time
watch).
25- OVERLOAD SWITCH: Connect the overload relay output to this input.
The relay will be of negative closing type in case of overload. This alarm will
cause the generator to release the load, but the engine runs until the end of
the cooling period.
26- ALTERNATOR HIGH TEMPERATURE SWITCH: Connect the high
temperature switch placed between windings of the alternator to this input.
WARNING: This switch shall be normally closed, and open in case of excess
of heat. If this input is not used, connect it to DC Supply negative terminal,
else an alarm will be given continuously. This alarm will cause the generator to
release the load, but the engine runs until the end of the cooling period.
27- OIL HIGH TEMPERATURE SWITCH: Connect the oil high temperature
switch to this input. This switch shall be negative closing switch type.
- 7 -