DUST FREE
LIGHTSTICK
®
INSTALL UV SAFETY VIEWPORT
• Adhere the provided UV duct label to the
outside of the duct near the installation
location and drill a 5/8" knockout as
indicated on the label. Press the UV safety
viewport into knockout.
• Close all access panels and reconnect
power to the air handler.
• Verify that a blue glow can be seen
through the UV safety viewport.
LAMP MAINTENANCE
• Each time the lamp is replaced, note
the date of lamp install and the next
recommended date of replacement on the
duct label.
• Lamp does not require any routine
maintenance, such as cleaning.
• Reference specifications page for lamp
replacement schedule and replacement
part numbers.
WARRANTY REGISTRATION
Register all new Dust Free equipment online
at https://dustfree.com/resources/warranty/
NOTICE
Replace Lamp Per Recommended
Maintenance Schedule.
UV-C lamps expend their germicidal
effectiveness over time. Replace the lamp even
if it appears to be operating normally.
INSTALLATION & OPERATION MANUAL
®
Fig. 15 Press viewport into place.
10