elsner elektronik KNX PS640+ Установка и регулировка - Страница 9
Просмотреть онлайн или скачать pdf Установка и регулировка для Источник питания elsner elektronik KNX PS640+. elsner elektronik KNX PS640+ 16 страниц. Systems
Также для elsner elektronik KNX PS640+: Технические характеристики и инструкции по установке (2 страниц)
Sprache
:Deutsch ™
Language
:English
Idioma
:Espanol
Taal
:Hollands
With key
you get back by one menu level to the basic setting.
Transmission protocol
Abbreviations
Flags:
C
Communication
R
Read
W
Write
T
Transmit
U
Update
Listing of all communication objects
No.
Name
0
Bus voltage [V]
1
Bus current [mA]
2
Permanent reset (1 = active | 0 = inactive)
3
Time reset
(1 = 30 seconds active | 0 = inactive)
4
Reset status of the line
(1 = active | 0 = inactive)
5
Overload (0 = normal | 1 = overload)
6
external overvoltage
(0 = normal | 1 = overvoltage)
7
internal overvoltage
(0 = normal | 1 = overvoltage)
8
Short circuit
(0 = normal | 1 = short circuit)
9
Overtemperature
(0 = normal | 1 = overtemperature)
10
System defect
(0 = normal | 1 = defect)
11
1 bit malfunction collection
(operation = 0 | fault = 1)
12
8 bit status collection
13
Date
14
Time
Move the cursor to the desired language with the up
and down keys and press the key
automatically jumps to the previous menu in the
desired language.
Function
Output
Output
Input
Input
Output
Output
Output
Output
Output
Output
Output
Output
Output
Input
Input
. The display
EIS type
Flags
14.030
C R T
9.021
C R T
1.003
C R W
1.003
C R W
1.002
C R T
1.002
C R T
1.002
C R T
1.002
C R T
1.002
C R T
1.002
C R T
1.002
C R T
1.002
C R T
5.010
C R T
11.001
C R W
10.001
C R W
9