This water heater must be installed by a licensed tradesperson, and in accordance with:
AS/NZS 3500.4 - "Plumbing and Drainage Code, Part 4: Heated water services".
AS5601/AG601 "Installation Code for Gas Burning Appliances and Equipment".
Local authority regulations.
Notice to Victorian customers from the Victorian Plumbing Industry Commission – this
water heater must be installed by a licensed person as required by the Victorian
Building Act 1993. Only a licensed person will give you a compliance certificate,
showing that the work complies with all the relevant Standards. Only a licensed person
will have insurance protecting their workmanship for 6 years. Make sure you use a
licensed person to install this water heater and ask for your Compliance Certificate.
Note: This water heater is not suitable for pool heating.
This water heater is designed for direct connection to water supply pressures up to
1100kPa. Where the mains pressure can exceed or fluctuate beyond 1100kPa, a pressure
limiting device (complying with AS1357) must be fitted in the cold water inlet supply. This
device must be installed after the isolating valve and set at or below 1100kPa.
Note: Ensure that the water heater is suitable for the available gas supply.
CAUTION: This water heater delivers hot water at temperatures exceeding 50
AS/NZS3500 and local regulations regarding the need for additional hot water delivery
temperature control.
The water heater should be located as close as possible to the most frequently used hot
water outlet. Adequate access must be made for service to the burner, gas control, relief
valve and anode.
Note: All models are equipped with a sacrificial anode, accessible through the top cover.
Allow 50% of the height of the water heater for clearance to replace the anode.
OUTDOOR Installation
The water heater should be installed with the minimum clearances as shown in Figure 1.
The water heater should be installed on a level, fireproof plinth at least 50mm above the
surrounding ground level. Position the two wall brackets 100 mm below the top of the unit
and secure them so that they are protruding approximately 10mm beyond the back of the
heater. Position the unit in place and secure the brackets to the wall (as per figure 1).
INSTALLATION DETAILS
LOCATION
4