Convoy Security DG333 Руководство пользователя - Страница 2

Просмотреть онлайн или скачать pdf Руководство пользователя для Пожарная сигнализация Convoy Security DG333. Convoy Security DG333 6 страниц. Wireless radio link a.c. wire-in photoelectric smoke and fire alarm with 9 volt battery back up

1. RECOMMENDED LOCATIONS FOR ALARMS
• Locate the first alarm in the immediate area of the
bedrooms. Try to protect the exit path as the bedrooms are
usually farthest from the exit. If more than one sleeping
area exists, locate additional alarms in each sleeping area.
• Locate additional alarms to protect any stairway as
stairways act like chimneys for smoke and heat.
• Locate at least one alarm on every floor level.
• Locate an alarm in every bedroom.
Locate an alarm in every room where electrical
appliances
are
operated(i.e.
humidifiers).
• Locate an alarm in every room where someone sleeps
with the door closed. The closed door may prevent the
alarm from waking the sleeper.
• Smoke, heat, and combustion products rise to the ceiling
and spread horizontally. Mounting the smoke alarm on the
ceiling in the center of the room places it closest to all
points in the room. Ceiling mounting is preferred in ordinary
residential construction.
• For mobile home installation, select locations carefully to
avoid thermal barriers that may form at the ceiling. For
more details, see MOBILE HOME INSTALLATION below.
• When mounting an alarm on the ceiling, locate it at a
minimum of 4" (10 cm) from the side wall (see Figure 1).
• When mounting the alarm on the wall, it is best to use an
inside wall with the top edge of the alarm at a minimum of
4" (10 cm) and a maximum of 12" (30.5 cm) below the
ceiling, (see Figure 1).
• Put smoke alarms at both ends of a bedroom hallway or
large room if the hallway or room is more than 30 feet (9.1
m) long.
• Install Smoke Alarms on sloped, peaked or cathedral
ceilings at or within 3ft (0.9m) of the highest point
(measured horizontally). NFPA 72 states: "Smoke alarms
in rooms with ceiling slopes greater than 1 foot in 8 feet
(.3m in 2.4 m) horizontally shall be located on the high side
of the room." NFPA 72 states: "A row of detectors shall be
spaced and located within 3 ft (0.9m) of the peak of the
ceiling measured horizontally" (see Figure 3).
FIGURE 1
DG333Manual
portable
heaters
or
Page 2 of 6
FIGURE 2
FIGURE 3
MOBILE HOME INSTALLATION
Modern mobile homes have been designed and built to be
energy efficient. Install smoke alarms as recommended
above, refer to RECOMMENDED LOCATIONS and Figure
1. In older mobile homes that are not well insulated
compared to present standards, extreme heat or cold can
be transferred from the outside to the inside through poorly
insulated walls and roof. This may create a thermal barrier
that can prevent the smoke from reaching an alarm
mounted on the ceiling. In such units, install the smoke
alarm on an inside wall with the top edge of the alarm at a
minimum of 4" (10 cm) and a maximum of 12" (30.5 cm)
below the ceiling (see Figure 1). If you are not sure about
the insulation in your mobile home, or if you notice that the
outer walls and ceiling are either hot or cold, install the
alarm on an inside wall. For minimum protection, install at
least one alarm close to the bedrooms. For additional
protection, see SINGLE FLOOR PLAN in Figure 2.
© 2008 CONVOY SECURITY