Terminal block
SIEMENS controller
Note,
1. The distance between SIMENS controller and DX AHU control box should less than or equal 15 m.
2. If several DX AHU boxes parallel connection control one indoor unit, SIEMENS controller only need to be connected with master DX AHU
box.
3. One SIEMENS can not control two or more indoor units at the same time.
4.All signals between SIEMENS controller and DX AHU box must be accord with the definition from table.9-1 and table.9-2. It will not work
correctly if the definition of signal in SIEMENS controller has been changed.
Normal
0.5
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9.5
M D4 D3 S Y1 M 14 13 34 44 54 53
Power
24V
MP 24V
SIEMENS
POL 638.70
13 14
23 24
Analog Input 0-10VDC
Range
Min
0
1.35
1.85
2.35
2.85
3.35
3.85
4.35
4.85
5.35
5.85
6.35
6.85
7.35
7.85
8.35
8.85
Y1
M
Y2
D1
M
D2
D3 M D4
INFO
ALARM
ESC
33 34
43 44
53 54
Room Temp. (
Cooling
Max
Not available
1.15
1.65
18
2.15
18
2.65
18
3.15
19
3.65
20
4.15
21
22
4.65
5.15
23
5.65
24
6.15
25
6.65
26
7.15
27
7.65
28
8.15
29
8.65
30
10
Not available
D5 M
63 64
Fig.9-4
Table.9-3
)
Room Temp. (
)
Heating
Not available
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Not available
installation manual