4. Terminal 37&38
These terminal connections will provide the status of this release device. When release device is in the standby mode, connection is
open (N/O). When release device have been activated or released, connection would be in closed (N/C) state.
5. See connection chart for power inputs.
Firefly IV MV
Terminals
Connection
Type
Power Input
High Voltage Alarm Signal
Low Voltage Alarm Signal
*Note: FACP – Fire Alarm Control Panel.
Connection Chart
Line In
High Voltage
L & N
Connect
115VAC or 230VAC
Connect Alarm Signal
115VAC or 230VAC
Do Not Connect
7
Low Voltage
41 & 42
(24VDC or 24VAC)
Connect
24VDC or 24VAC
(Voltage supplied by FACP
or an UL listed power supply)
Do Not Connect
Connect Alarm Signal
24VDC or 24VAC
(Voltage supplied by FACP)
Alarm Connection
31&32
Connect FACP*
Alarm Dry Contact
(5.16 ohms max line
impedance)
Jump
(Wire size min 18AWG)
Jump
(Wire size min 18AWG)