Austro Flamm Dexter 2.0 L Руководство по эксплуатации - Страница 5
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Плита Austro Flamm Dexter 2.0 L. Austro Flamm Dexter 2.0 L 11 страниц.
english
7
Dexter
Flue Installation
Flue type: Triple skin flue, 150mm Active /200mm/250mm Double Casing, ie 6"/8"/10". The Active 150mm flue must be a
tight fit into the heater collar.
The heater must have its own dedicated flue. The active flue must be 8" for the entire length of the flue, and always
less than 45 degrees from the vertical.
Replacement room air from outside equivalent to 160cm2 must be supplied into the room.
Flue Outlet Positions
Minimum Flue Height as per AS/NZS 2918:2018
NOTE: Flue exit MUST also be as high as any nearby structure within a 6m Radius. ( AS 2918:2018 )