Electrical connection:

LED operating status display
Fault display
!
LED off:
Fault relay "Off"
LED flashes:
Fault relay "On"
LED illuminated: Fault confirmed but not cleared (fault relay "Off")
Cooling request
=
LED off:
Cooling relay "Off"
LED illuminated: Cooling relay "On"
Cooler fan
§
LED off:
Fan relay "Off"
LED illuminated: Fan relay "On"
Defrost request
LED off:
Defrost relay "Off"
$
LED illuminated: Defrost relay "On"
LED flashes:
On hold (defrost relay "Off")
Entry status
LED off:
When moving through the menu
/
LED illuminated: When a menu item is open and the setting is
displayed
LED flashes:
When a menu item's setting is changed
Operating state for digital input 1
%
LED illuminated: Floating contact at terminal 1 and 2 closed
Operating state for digital input 2
&
LED illuminated: Floating contact at terminal 1 and 3 closed

Control buttons

Control button 1
>
Move upwards in the menu or increase the value
Control button 2
<
Move downwards in the menu or decrease the value
Handling and operation
The control is operated using two buttons. The control is set on three main
operating levels: the user level, the configuration level and the statistic level.
Within the operating levels, the menu items are shown in the display using
abbreviations. The menu items are selected by pressing the control buttons. A
selected menu item will show its setting alternately after 5 sec. To change to the
other operating level, set the appropriate menu item and press both buttons at the
same time.
To make a setting or a change, the selected menu item must be opened by
pressing both buttons at the same time. The "Entry Status" LED lights up and the
current setting is displayed. Pressing the control buttons allows a setting or
change to be made within one of the opened menu items.
A deviation from the last saved setting is shown when the "Entry Status" LED
flashes. Pressing both buttons at the same time closes and saves the changed
menu item. The "Entry Status" LED is switched off, thus confirming that the setting
has been correctly completed. After 5 sec. the new setting is shown alternately
with its menu item. After changing from operating level "-2-" or "-3-" to operating
level "-I-", the room temperature "tL1" is automatically shown.
Note:
If an open menu item remains unclosed, it will close automatically after 5 minutes.
The last saved setting remains unchanged. You are automatically taken back to
operating level "-I-" to the display of the room temperature "tL1".
TL1
TBL
The power supply of AC/DC 24 V may only be connected to the input terminals 4
and 5 provided for this purpose. Incorrect connection results in immediate
destruction of the control.
The digital inputs 1 and 2 and the input terminals 1, 2 and 3, as illustrated here,
may only be switched with floating contacts.
External voltage of any kind results in immediate destruction of the control and can
lead to fatal injury if disregarded. This also applies to the Pt 1000 sensor inputs
TL1 and TBL, terminals 6 to 10.

Display and control elements

Starting operation
Initialization of the control:
:888
LED function test
cE3
Device name
r19
Control version
. 1
Control subversion
. 3 8
Software version
Display of the configured temperature scale
Configured temperature scale is displayed for a short time
°C
("°C" or "°F")
Display of network module identification code
The identification code of the network module is
IF3
displayed temporarily. This message is only visible when a
network module is installed.
Normal operation after initialization
The room temperature is displayed
: 0. 5
after initialization
Note:
Alerts detected by the control also remain stored, even in the event of a power
failure, and are displayed again when power is restored (fault display LED, alert
and buzzer). Alerts can only be deleted under the menu item "ALt" with "cLr".
If the Power fail control "PFC" is set to "On", thus switched on, the alert "PFL" is
displayed when power is restored.
3