Bender NGRM750 Краткое руководство по эксплуатации - Страница 7

Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Монитор Bender NGRM750. Bender NGRM750 8 страниц. Neutral grounding resistor monitor (ngr)

2. System settings of the relays (menu 6.6)
The factory setting for the relays is fail-safe.
In the case of a test, the relays change state.
i
Fail-safe: The relay is energized during normal op-
eration and is de-energized
in the event of a fault
("fail-safe")
Non-fail-safe: The relay is de-energized in normal
operation and is energized in the event of a fault
("non-fail-safe")
3. Field calibration (menu 6.7)
During field calibration, all tolerances of the connected
CD-series coupling device and the NGR are considered.
The current measured value is calibrated to the set nomi-
nal value of the NGR (R
curacy, start the device and let it run for at least one hour
in the operating environment before carrying out the
field calibration.
i
For the field calibration the device must be in auto
mode (menu 6.3.1 = auto).
If the digital input I1 is used with "Digital 1 > NGR
method" (menu 6.6.5.3), "Method > external" (menu
6.3.1) must be selected and I1 must be active (see
manual).
The trip relay is switched during field calibration!
4. RMS trip signal, fundamental frequency, har-
monics
The measured value which causes tripping can be select-
ed via the "Trip signal" parameter (menu 6.5.11). Trip sig-
nal can be:
• RMS: The RMS value of I or U over the entire fre-
quency range (up to approx. 3.8 kHz).
• Fundamental frequency: Only the RMS value of the
fundamental frequency (50 or 60 Hz).
• Harmonics: The filtered RMS value on the selected
range of harmonics with
H0 = DC; H1 = fundamental frequency; H2 = 2 x funda-
mental frequency; ... H32 = 32 x fundamental frequency
i
In the "Harmonics" measured value display (menu
2) all spectral lines are always displayed. This is in-
dependent of the trip signal setting.
i
On the standard display, the trip signal is indicat-
ed as resistance (in Ω or %) or as current (in A or
%). The setting is entered in "Display" (menu 5).
). In order to achieve high ac-
NGR nom
5. Initial measurement
During device start, all measured values are recorded.
Factory settings
Menu
Menu 6.1: HRG/LRG system
1. U
sys (L-L)
2. CD-NGRM
3. Frequency
4. I
NGR nom
5. R
NGR nom
Menu 6.2: CT
1. CT primary
2. CT secondary
3. CT connection
Menu 6.3: NGR
1. Method
2. Filter
Menu 6.4: Phase monitor
1. Phase monitor
2. PT primary
3. PT secondary
Menu 6.5: Response values
HRG
1. U
NGR Trip
2. I
NGR Trip
3. > R
NGR
4. < R
(HRG only)
NGR
5. t
4. t
NGR trip
NGR Trip
6. Ground-fault trip
5. Ground-fault trip
7. t
6. t
GF Trip
GF Trip
8. Alarm stored
7. Alarm stored
9. t
8. t
restart
restart
10. Max. no. of restarts 9. Max. no. of restarts
11. Trip signal
10. Trip signal
12. Upper limit
11. Upper limit
harmonic
harmonic
13. Lower limit
12. Lower limit
harmonic
harmonic
NGRM7xx_D00292_07_Q_XXEN/11.2022
NGRM700 (HRG), NGRM750 (LRG)
Factory settings
400 V
CD1000
50 Hz
5 A
470 Ω
600
1
50 mA
auto
off
on
1
1
LRG
60 %
60 %
150 % (HRG),
250 Ω (LRG)
50 %
0 s
yes
5 s
on
5 s
2
RMS
32
0
7