BASIC INFORMATION
INTENDED USES
These engine generator sets have been designed primarily
for portable use. Both 120 and 240 volt AC receptacles are
provided in the 'control panel' to plug in your loads (lights,
portable tools, and small appliances). These units are
dual wound generators, therefore the 120 Volt loads must
be equally split with 1/2 of the rated capacity available on
each of the two 120 Volt circuits. See unit capabilities for
further explanation.
These portable units require large quantities of fresh air for
cooling of both the engine and the generator. Fresh air is
drawn from both the engine end and the generator end and
is exhausted at the center of the unit. For safety, long life
and adequate performance, these units should never be
run in small compartments without positive fresh air flow.
RESTRICTED USES
DO NOT remove from the cradle assembly. Removal of the
generator from the cradle assembly may cause excessive
vibration and damage to the engine generator set.
DO NOT install and operate these portable generators in a
small compartment., i.e. generator compartment of
vehicles, motor homes or travel trailers. These
compartments will not allow enough free flow fresh air to
reach the engine generator set for cooling and will cause
the unit to overheat damaging both the engine and the
generator. Small compartments will also develop hot
spots where there is very little air flow and may cause a fire.
DO NOT attempt to operate at 50 cycles. These units are
designed and governed to operate at 60 Cycles only.
UNIT CAPABILITIES
Generator Connections - The diagram below represents a
typical 4000 watt generator. Receptacles A and B are the
two 120 Volt duplex receptacles. Up to 2000 watts at 120
volts (16.6 Amps) can be taken from the generator at each
of the receptacles. This generator produces 120 and 240
volt, 60 Hz (Hertz), AC (Alternating Current).
CAUTION: EQUIPMENT DAMAGE
CAUTION MUST BE EXERCISED TO PREVENT
OVERLOADING EITHER OF THE GENERATORS
120 VOLT OUTPUT CIRCUITS (A OR B).
60707-110
Check the appliance or tool nameplates for the current and
voltage to insure compatibility. Remember that power taken
from receptacle C reduces the power available at both A and
B. Any remaining 120 volt loads should be equally divided
between A and B. Failure to split the load will cause
permanent damage to the stator. Although circuit breakers
are provided, damage due to overloading constitutes abuse
and will not be warranted. Refer to the generator nameplate
for your unit's capabilities.
Starting Electric Motors - Electric motors require much more
current (amps) to start them than to run them. Some motors,
particularly low cost split-phase motors, are very hard to start
and require 5 to 7 times as much current to start them as to
run them. Capacitor motors are easier to start and usually
require 2 to 4 times as much current to start them as to run
them. Repulsion Induction motors are the easiest to start
and usually require 1 1/2 to 2 1/2 times as much to start them
as to run them.
Most fractional horsepower motors take about the same
amount of current to run them whether they are of Repulsion-
Induction (RI), Capacitor (Cap), or Split-Phase (SP) type. The
chart below shows the approximate current required to start
and run various types and sizes of 120 volt 60 cycle electric
motors under average load conditions.
RUNNING
HP
AMPS
1/6
3.2
1/4
4.5
1/3
5.2
1/2
7.2
1
13.0
The figures given above are for an average load such as a
blower or fan. If the electric motor is connected to a hard
starting load such as an air compressor, it will require more
starting current. If it is connected to a light load, or no load
such as a power saw, it will require less starting current. The
exact requirement will also vary with the brand or design of
the motor.
Self-excited generators respond to severe overloading
differently than the power line. When overloaded, the engine
is not able to supply enough power to bring the electric motor
up to operating speed. The generator responds with high
initial starting current, but the engine speed drops sharply.
The overload may stall the engine. If allowed to operate at
very low speeds, the electric motor starting winding will burn
out in a short time. The generator winding might also be
damaged.
CAUTION: EQUIPMENT DAMAGE
RUNNING THE GENERATOR SET UNDER THESE
CONDITIONS MAY RESULT IN DAMAGING THE
GENERATOR STATOR AS WELL AS THE MOTOR
WINDING.
Because the heavy surge of current required for starting
motors is required for only an instant, the generator will not
be damaged if it can bring the motor up to speed in a few
seconds of time. If difficulty is experienced in starting motors,
turn all other electrical loads off and if possible reduce the
load on the electric motor.
Page 3
STARTING AMPS
SP
CAP
16 TO 22
6 TO 13
5 TO 8
22 TO 32
9 TO 18
7 TO 12
26 TO 35
10 TO 21
8 TO 17
NOT MADE 14 TO 29
11 TO 18
NOT MADE 26 TO 52
20 TO 33
DYNA SERIES 5/97
RI