NETWORKING/ GANGING
Cabinet can be networked using the G101ES
GROUNDING
GROUNDING KIT, GR101
Grounding studs in our EZ cabinet provide
a point to which the doors may be grounded to the
cabinet and from which the cabinet may be
connected to the facility's common ground.
Using the grounding straps supplied, connect one
end of the strap to copper ground stud on the side panels
and/or doors and the other end to copper ground
stud on the frame of the cabinet. Once all
straps have been connected to a copper frame
stud, have at least one frame stud connected to
the common building ground.
COPPER BUS BARS, CBB-72
It is important to note that grounding the cabinet
does not ground the equipment mounted within it.
In order for any individual devices and
components mounted within an cabinet
to be grounded, they must be
connected to a copper bus bar.
Washer
Lock Washer
Wing
Nut
No Tools Required!
Ground Stud:
#10-32 x 1 7/8 LG
or M6 x 50mm LG
#10-32 Nut
Insulator
#10-32 Nut
Washer
Thumb
Screws