Battery Temperature Compensation Charge
Connecting the cable RJTEMP (supplied separately) to Auxiliary Output
AUX1, the CBI will adjust the battery charging voltage in relation to the
Battery temperature:
Fast Charge: Open Lead, AGM, Gel
+/- 5mV/°C x n. of Cells from -8°C to +60°C
+140 ÷ -200 mV/Cell compared to the value at
20°C
Fast Charge: Ni-Cd
+/- 2.5 mV/°C x n. of Cells from -20°C to +60°C
+100 ÷ -100 mV/Cell compared to the value at
20°C
The device stops charging the battery if the temperature is below -20°C
or above +60°C. The sensor placed on cable RJTEMP must be applied
on the battery.

Device Configurations

Completely automatic, all devices are suitable to charge most batteries
types thank to User Selectable charging curves. They can charge open
lead acid, sealed lead acid, Gel, Ni-Cd and Li-Ion. It is possible to change
or add other charging curves connecting the web server device to a PC.
Configurations
Note: it is also possible to configure the device via Web server
In normal operation the LED bargraph (No.19 in sect.7) gives an
indication of the current (0 to 100% of In) as follows:
In charge mode with mains:
battery charge current with solid light
In backup mode without mains: battery discharge current with
blinking light
In boost mode with mains: battery discharge current with
flickering light
To display the current device configuration on the LED bargraph press
the Config/Start button (No.9 in sect.7) briefly (< 1 sec). The display
returns to normal operation after 10 seconds. Please refer to the pictures
at the end of this section.
To change the device configuration, complete the procedure below (note:
if the procedure is not completed no settings are saved; the procedure is
aborted if no command is given for 60s).
With battery disconnected:
press the Config/Start button (No.9 in sect.7) for more than 2
seconds, until the first led starts blinking
press briefly the button to cycle through the battery types as
shown by LEDs 1,2,3 (please refer to the pictures at the end of
this section) then confirm with a long press until the 4th LED starts
blinking
LED 4: Config Mode: ON/OFF
Long press to enable a complete configuration via Web Server,
Modbus/SNMP and APY351/ADELViewSystem (Led ON).
Short press to configure basic parameters from the device front
panel or from the web server System page (Led OFF)
If Config Mode was selected, the procedure terminates here
LED 5: Option: not used: continue with a short-press
LED 6: Life Test; long press to enable the function (Led ON), short
press to disable
LED 7: Fast Charge; long press to enable the function (Led ON),
short press to disable
LED 8: UPS Disable; long press to disable the UPS function (Led
ON), short press to keep it enabled
LED 9: Buffering time: press briefly the button to select the max
backup duration, then confirm with a long press. The current
selection is shown with other LEDs blinking together with LED 9
as follows:
Led 1: 30 sec; Led 2: 120 sec; Led 3: 300 sec; Led 4: 10 min; Led
5: 15 min; Led 6: 20 min; Led 7: 30 min; Led 8: 45 min; All leds:
Infinite time
Note: the last selection (infinite time) is confirmed automatically
also with a short press
More values can be selected by Web Server, Modbus, SNMP and
with DPY351 or ADELVIEWSystem
End Programming: the device shows the selected configuration
for 10 seconds then resumes normal operation,
With battery connected:
press the Config/Start button (No.9 in sect.7) for more than 2
seconds, until the 5th led starts blinking
follow the procedure above from step "LED 5: Option" (Battery
Type and Config Mode can be changed only when the battery is
not connected).
Float charge: Open Lead, AGM, Gel
+/- 3mV/°C x n. of Cells from -20°C to +60°C
+120 ÷ -120 mV/Cell compared to the value at 20°C
Float charge: Ni-Cd
+/- 2.5 mV/°C x n. of Cells from -20°C to +60°C
+100 ÷ -100 mV/Cell compared to the value at 20°C
Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy
Tel. +39 0522 345518 – Fax +39 0522 345551 –
Battery Type chemistry Selection
LED Config
(Size 5)
Open Lead
(AGM) Low
Gel Battery
Ni-Cd
Li-Ion (4)
LiFePo4
Config Mode (5)
Functional Setting
Battery Life
test ON
Fast Charge
Enable (3)
UPS Disabling
Time Buffering
"Start from
Battery" (No
Input Mains)
Data and Communication
ADELBus connection
Remote device connection by terminals 22. This device features the
ADELBus communication protocol for the connection of other devices on
CAN bus, for monitoring, configuring, driving and updating them(fig.3).
www.adelsystem.com
Instruction Manual CBI60_4
Float charge
Fast charge
(Volt/Cell)
(Volt/Cell)
2.23
2.40
2.25
2.40
2.30
2.40
1.4V/cell
1.45V/cell
(12V:10 cells)
(12V:10 cells)
(24V:20 cells)
(24V:20 cells)
(48V:40 cells)
(48V:40 cells)
3.45V/cell
3.65V/cell
12Vfield: 13.8V
12Vfield: 14.6V
24Vfield: 27.6V
24Vfield: 29.2V
48Vfield: 55.2V
48Vfield: 58.4V
Configure with ADELViewSystem or Web
Server for CBI60
Life test enabled
Fast Charge enabled.
UPS function enabling. Use terminal 12 for
connection to external Contact.
1 blink => 0.5, 2 blink => 1,
3 blink => 5, 4 blink => 10,
5 blink => 15, 6 blink => 20,
7 blink => 30, 8 blink => 45 min
9 Solid =>
infinite"
(Time = minute)
System switch ON from battery without
mains. For connection to external Push
button use terminal 12