The cabling for this connector should be constructed according to the characteristics
described:
Description
Nom. Diff. Characteristic Impedance
Nom. Inductance @ 10 kHz
Nom. Capacitance – Conductor To Conductor @
10 kHz
Nom.
Capacitance
Conductor & Shield @ 10 kHz
Nom. Velocity of Propagation
Nom. Conductor DC Resistance @ 20C
Nom. Outer Shield DC Resistance @ 20C
Max. Operating Voltage – UL

2.5.4 Mode Dip switch SW2

With the DIP switch 2 the user can change the IP address from the device, select if the
communication is unicast or multicast, change the IP multicast address and select to use
the default Ethernet settings or to use the user configured settings.
By default, YAV90090 will have the following IP addresses:
• IP address: 192.168.18.55
• Net mask: 255.255.255.0
• Gateway address: 192.168.18.10
• Multicast IP address: 224.0.0.5
NOTE: YAV90090 can handle any other IP configuration, contact with 6TL
Engineering for more information.
Conductor
To
Other
Ethernet to CAN Gateway YAV90090 620090E06
Value
100 ohms (+10 ohms, -15 ohms)
0.47 uH/meter
41.0 pF/meter
65.6 pF/meter
74%
14.57 ohms / 100 meters
1.7 ohms / 100 meters
30 V RMS
Pin
Function
1
Tx+
2
Tx-
3
Rx+
4
-
5
-
6
Rx-
7
-
8
-
9