7bit Synapse Руководство по эксплуатации - Страница 2

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Пульт дистанционного управления 7bit Synapse. 7bit Synapse 2 страницы. Mqtt/modbus tcp/8di/8do(r)/32x1-wire/ac industrial digital input/output module for remote process control and data acquisition

7bit Synapse Руководство по эксплуатации
Address
Description
HR111 ~ 118
DO1 ~ 8 PWM duty cycle
3.6 Predictive maintenance functions (changeover & time on counters)
Power on cycles and run hours may reduce life-time of the equipment under monitor.
Now it is possible to count them using Synapse onboard counters and totalizers:
Address
Description
HR0 ~ 14
DI 1 ~ 8 changeover counters
HR60 ~ 74
DI 1 ~ 8 time on totalizers
HR76 ~ 90
DO 1 ~ 8 changeover ounters
HR92 ~ 106
DO 1 ~ 8 time on totalizers
3.7 1-Wire connection The Synapse provides connection for up to 32 digital
temperature sensors DS18B20 via 1-Wire bus with a maximum length 200 m, as shown
at figure below.
Bus topology. Up to 200 meters.
Auto enumeration for 1-Wire sensors. Each DS18B20 has their own unique serial
number. Using a special search algorithm, the Synapse finds and saves the
enumeration scheme for the sensors found in the static memory. New sensors still can
be added to the existing enumeration by:
powering on or resetting the module
writing non-zero value into HR33 register
Address
Description
IR0 ~ IR31
Temperatures 1 ~ 32
HR33
Total sensors quantity / Init**
* -1000 is displayed if a sensor is not present or damaged
** writing 0 to HR33 clears the enumeration.
4. Configuration
The factory network default settings for the Ethernet interfaces is a DHCP client. So,
after power on and plugging it into your router network it automatically will be added
to your network. You may setup a static DHCP lease for the module, or use manual IP
network setup.
4.1 Configuration mode for IP settings When you have a device with unknown
address and want to make quick IP setup, switch the module to the CONFIGURATOIN
MODE. Hold the reset button during reboot for a few seconds (status LED will be
blinking frequently). The module will start with 192.168.4.1 address. In this mode you
can change setting either with Configuration Web server or with Modbus setting
registers. To switch back to normal mode, reboot the module.
4.2 Configuration Web server In the configuration mode, there is Configuration
web-page available on the 192.168.4.1. Instead of Modbus register, you can use this
page for module setup. The page can be switched off during setup. To enable it again ,
use the following register:
Address
HR39
Data
R/W
Default
W
R/W
0 (No)
Data
R/W
Default
DW
R/W
-
DW
R/W
-
DW
R/W
-
DW
R/W
-
IP configuration It can be done either with the web page or the Modbus registers:
Address
HR40
HR41 ~ HR44
HR45 ~ HR48
HR49 ~ HR52
MQTT configuration
Data
R/W
Default
W
R
-1000*
W
R/W
0
5. Diagnostics
The normal LED state upon power on is as follows:
red POWER - always on.
green SYSTEM – is blinking once a second (two times faster in configuration
mode)
yellow 1WIRE – blinks when the sensors are polled
The DI/DO LEDs reflects the actual signal states on terminals. During normal boot
process, DI/DO ticks in series.
Use "ping" command to check network connection and Modbus/MQTT testing tools
to test the protocol connection.
In case of troubles with adding temperature sensors, the most probable cause is the
length of 1-Wire bus or its topology (signal or power attenuation, caused too long line,
Description
Data
R/W
Configuration Web server enable
W
R/W
Data
R/W
Description
Static IP enable
W
R/W
IP address octets (x.x.x.x)
W
R/W
Mask octets (x.x.x.x)
W
R/W
Gateway IP address
W
R/W
octets
Visit level2.webhmi.com.u a to learn
about IoT applications with Synapse
MQTT capability.
Use ready "New device"
tool to quickly create your register set in
Level2 / WebHMI projects.
interference due to side branches etc.). First of all, try to connect sensors with short
Default
1 (yes)
wires. If ok, then check wiring (refer to general Maxim 1-Wire recommendations).
Synapse has internal watchdog, which may reboot the device in case of accidental
malfunction. Refer to the following diagnostic registers to check if failures might have
occurred.
In a case the device doesn't working properly, please contact to your supplier.
Address
HR30
Reboot counter
HR31, HR32
Uptime, sec. (low, high)
HR34
Free memory
6. For more information
If you have any questions or problems related to the operation of the 7Bit™
products, please contact to the unified support service +38 (056) 796-96-90,
7. Warranty
The company of "Distributed Data Systems LLC", the manufacturer of 7Bit Synapse IO
Default
module (hereinafter referred to as the Manufacturer), expresses its great gratitude for
0(no)
your choice. We did our best to ensure that this product met your requirements, and
192.168.1.2
the quality corresponded to the best standards. The manufacturer sets the life of the
Synapse IO module to 10 years in case of its proper usage. The service life is calculated
255.255.255.0
from the date of manufacture of the requirements for warranty obligations and for
free repair (replacement of the product) in the case of failure to comply with the
192.168.1.1
conditions set forth below. All the terms of the warranty and free repair (replacemen t )
are in force under the law on consumer protection.
The manufacturer sets a warranty period, counted from the date of sale, and the
period of free repair (replacement), subject to compliance with the rules of operation,
12 months. Replacement of defective parts (assemblies, assembly units) in the product
during the warranty period does not lead to the
establishment of a new warranty period for the entire product, or for replaced parts.
The manufacturer declines all responsibility for the possible harm, directly or indirectly
caused by the Synapse device to people, animals, property in case event that this is
the result of non-compliance with the rules and conditions of use of the product;
Intentional or reckless actions of the buyer
(consumer) or third parties. Also, the Manufacturer declines all responsibility for the
possible damage, directly or indirectly caused by the Synapse device as a result of
alteration, damage, loss of data and information
Date of the manufacturer's QA _____________________________
Date of sell _____________________________________________
Sellers marks ___________________________________________
Buyer's signature ________________________________________
Description
Data
R/W
Default
W
R
-1000*
W
R
W
R
Synapse Quick guide fw ver.: 1.05
07.21