Setting Limits
2.1
Setting/Adjusting Limits after Initial Power Up
For first time users it is recommended not to use section 2.1. Please go back to
STOP
section 2.0 and go through the step by step procedure.
DYNACO USA, INC,
TIMERS
OPEN
JOG
UP/RESET
JOG
MC/PB
DOWN
CLOSE
TIMERS
MENU
Figure 2.0-5: JOG UP/RESET Button
12. Press and release the ENTER button to save limit setting. Display will
change to: PhtLimit_Set—OK.
13. Press and release either red arrow buttons to scroll to the OpnLimit.
14. Press and release ENTER button. Display will change to:
JogToOpn_Enter.
15. Use the JOG UP/RESET button to bring door up desired open position
(roughly a inch and a half above the reintroduction point).
16. Press and release ENTER button to save limit setting. Display will change
to: OpnLimit_Set--OK
17. Press and release the MENU button twice. Display will change to: Ready.
See figure: 2.0-6.
TIMERS
OPEN
JOG
UP/RESET
JOG
MC/PB
DOWN
CLOSE
TIMERS
MENU
Figure 2.0-6: Menu Button
RUN
CLOSE
PROGRAM
AC/LOOP
ENTER
RUN
CLOSE
PROGRAM
AC/LOOP
ENTER
The Leader in Door Safety & Design
5
Press the
JOG UP/RESET
button to bring
door up
MESSAGE DISPLAY / COUNTER
JogToPht
Enter
Press and
release the
MENU button
twice to exit
program
mode
MESSAGE DISPLAY / COUNTER
Ready
###