1. Turn the Johnson panel power switch off.
2. Determine the type of signal received by
the field termination board. Consult the
Johnson Controls manuals if necessary.
The InterOP8500 must be configured to
receive the same type of input as the
previously removed Johnson boards.
3. Set the InterOp8500 jumpers as follows:
• For RTD mode insert a jumper for the
individual input. The jumpers are
located along the lower right side of the
InterOP8500 board (see Figure 13).
NOTE
NOTE
NOTE
NOTE If using a solid-state current
switch on a digital input, the resistance
must drop low enough for the module to
recognize it.
• For voltage and potentiometer mode,
remove the jumpers. (Current mode can
be configured by adding an external
As specified by the
sensor manufacturer.
Isolated
DC Power
Supply
XX VAC
120 VAC
ungrounded
Revised 7/10/01 • InterOP8500
Field Termination
Board
Sensor
4-20mA
250 ohm
Transducer
resistor
Figure 14. Analog Input Wiring for 4-20 mA Signal
sense resistor. For 4-20mA use a 250
ohm resistor Figure 14). Turn the
InterOP8500's power switch on.
Unsw itched Inputs
Jum p er in P la ce =
RTD M o d e
Sw itched Inputs
Jum p e r R e m ove d =
V oltag e Mode
Figure 13. Analog Input Jumpers
Connect to Analog Input
Connect to Analog Common (unswitched)
11