Automated Logic M220NX Технические инструкции - Страница 8

Просмотреть онлайн или скачать pdf Технические инструкции для Блок управления Automated Logic M220NX. Automated Logic M220NX 9 страниц.

Automated Logic M220NX Технические инструкции

Transferring Memory

The M220nx module can store up to 14
Function Blocks (FBs) and the M2M module
driver. If you have any problems transferring
memory to the module, contact Technical
Support at (770) 429 3002.
1. Log in to SuperVision on a workstation
connected to the CMnet. You can also
connect directly to the module using the
Access Port; see "Communicating with the
Workstation" on page 5.
2. Navigate to the module driver and look at
the module status report in SuperVision to
make sure the module type and number
agree with the module.
• To view the module status report in
SuperVision v3.0, click Tools-
Troubleshooting-Module Status.
• To view the module status report in
SuperVision v2.6b, press the Esc key,
type MO
, , module address,15
and press Enter.
3. Transfer memory to the module.
• In SuperVision v3.0, click Tools-
Troubleshooting-Transfer Memory to
Module.
• In SuperVision v2.6b, choose Download
Memory for This Module.
4. When the memory transfer is finished,
check the module status report again.
Make sure the FB List on this page shows
all the FBs you intended to transfer.

Troubleshooting

Formatting the Module

When you are unable to communicate with a
module, you can, as a last resort, manually
format the module to try to restore
communication. Formatting the module
erases all memory, so you need to transfer
Revised 4/3/00 • M220nx
memory back to the module once it is
formatted.
1. Turn the module's power off. Make sure
the module's address switches are not set
to '0,0'.
2. Press and hold the Format button (see
Figure 1 on page 2 for location).
3. While continuing to hold the Format
button, turn the module's power on.
4. Continue to hold the button until the Error
LED flashes three times in sync with the
Run LED.
5. Release the Format button.
6. Transfer memory to the module. Refer to
"Transferring Memory".

LEDs

The M220nx module has several LED
indicators to show the status of certain
functions. Table 5 explains the Run and Error
LED signals in detail to assist troubleshooting.
Table 5. LED Signals
Run LED
Error LED
2 flashes
Off
per second
2 flashes
1 flash per
per second
second
2 flashes
2 flashes
per second
alternating
per second
2 flashes
2 flashes in
per second
sync per
second
2 flashes
3 flashes
per second
per second
2 flashes
4 flashes
per second
per second
2 flashes
On
per second
5 flashes
On
per second
8
© 2000 Automated Logic Corporation
Condition
Normal
Normal, but module is
alone on the CMnet
Five minute auto-restart
delay after system error
Module is configured for a
different baud rate than the
rest of the CMnet
Module has just been
formatted
Two or more items in the
database have the same
ARC156 CMnet address
Exec halted after frequent
system errors
Exec start-up aborted, Boot
is running