Using the MX800
The MX800 is part of the M-Line, which
allows a complete controls system to be built
a piece at a time. By attaching the MX800
expander to M or Mcpu controllers, your
system can grow as the size of the job
increases. The MX800 has eight digital
outputs.
The MX800 provides the communications
circuitry and removable screw terminals for
I/O connections.
CAUTION Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
user's authority to operate equipment.
NOTE This equipment has been tested and
found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide
reasonable protection against harmful
interference when the equipment is operated
in a commercial environment. This
3 25/32"
9.6cm
1/4"
0.6cm
Revised 3/29/00 • MX800
11 5/16"
28.73cm
I/O
Expansion
Run
Expander
I/O
MX800
POINT EXPANDER
C AUT IO N:
T o Red u ce the Risk of Fir e
o r E le ct ric al Sh ock ,
D o Not In ter conn ect T he
Ou tput s of Dif fe ren t
C lass 2 Circui ts
Digital Outputs
24V Max.
3A Max.
NC
Expander
Address
I/O
Expansion
Rotary
I/O
Address
Expansion
Figure 1. Module Dimensions and Layout
2
equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual, may cause harmful interference to
radio communications. Operation of this
equipment in a residential area is likely to
cause harmful interference in which case the
user will be required to correct the
interference at his own expense.
Specifications
Power 24VAC ± 10%, 50-60Hz (24VAC
±10%, 60Hz for UUKL Smoke Control
Systems), 20VA power consumption
single Class 2 source only, 100VA or less.
Digital Outputs eight digital outputs,
relay contacts rated at 3A resistive @
24VAC. Configurable as normally open or
normally closed.
Environmental Operating Range 0° to
130°F (-17.8° to 54.4°C); 10 to 90%
relative humidity, non-condensing. (For
UUKL Smoke Control Systems, 32 to
120.2 °F [0 to 49 °C]; 10 to 85% relative
humidity, non-condensing.)
Power
On Of f
Gnd
C l a s s 2
24 Vac
2 4 V a c , 5 0 - 6 0 H z
2 0 V A , 0. 8 3 A
U s e C o p p e r
C o n d u c t o r s O n l y
16
DO-8
15
14
DO-7
13
12
DO-6
11
10
DO-5
9
8
DO-4
Switches
7
6
DO-3
5
4
DO-2
NO
3
2
DO-1
1
Auto Off On